– 21 –
SUPPLEMENTARY
POWER SUPPLY
+
–
COMMUNICATOR
TERMINAL STRIP
AUX AUX. DATA DATA
+
–
IN
OUT
11
12
13
14
IMPORTANT:
MAKE CONNECTIONS
DIRECTLY TO SCREW
TERMINALS AS SHOWN.
TO KEYPAD RED WIRE
TO KEYPAD BLK WIRE
TO KEYPAD YEL WIRE
TO KEYPAD GRN WIRE
TO KEYPAD RED WIRE
TO KEYPAD BLK WIRE
TO KEYPAD GRN WIRE
TO KEYPAD YEL WIRE
IMPORTANT:
Make connections directly to screw
terminals. Make no connection to
the keypad blue wire (if present).
Figure 5. Using A Supplementary Power Supply For Keypads
Mounting the Keypads
1.
Mount the keypads at a height that is convenient for the user. Refer to the
instructions provided with the keypad for mounting procedure.
You can either surface mount or flush mount keypads (using the 6139TRK
Trim Ring Kit ). Refer to the mounting instructions and template included with
the keypad and/or trim ring kit for specific information.
Addressing the Keypads/Preliminary Check-out Procedure
If you want to check that the system is working before connecting field wiring
from zones and devices, do the following:
1. Temporarily connect a 2000 ohm end-of-line resistor across each of the basic
hard-wire zones 1–8, as shown in the Summary of Connections diagram.
Without actual zone wiring or EOL resistors connected, the keypads will not
display the “Ready” message.
2. Power up the system temporarily.
The keypads will not operate until they are physically addressed and enabled in
the system's Device Programming Mode.
3. Set each keypad to an individual address (00-30) according to the keypad's
instructions. Set an alpha keypad for address "00" and other keypads for
higher addresses (01, 02, and 03 are enabled in the system's default
program). Any keypads set for address 04 and above will appear blank until
they are enabled in the system's program.
Keypads set to the non-addressable mode (address 31) will interfere with other
keypads (as well as other devices) connected to the keypad terminals.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...