– 77 –
Section 13. EXTERNAL SOUNDERS
This section provides the following information:
•
General information about the bell outputs
•
Bell circuit supervision
•
Programming the bell outputs
•
Wiring alarm notification devices
General Information
The VISTA-100 provides two bell circuit outputs for operating fire and burglary
alarm notification appliances. Each bell output is rated as follows: 10VDC -
14VDC, 1.7 amps max., power limited. Note that the total alarm current drawn
from the Aux Power 1, Aux Power 2, polling loop, Bell 1, and Bell 2 outputs
cannot exceed 2.3 amps for battery independent operation. Each output has the
following options:
•
Class B supervision (Style Y) or no supervision
•
Selectable to activate by individual zone assignments
•
Selectable for Confirmation of Arming Ding (1-2 sec. sounding to
confirm
system has armed)
•
Selectable to chime when Entry/Exit or Perimeter zones are faulted
•
Selectable for steady or pulsing output
•
Selectable for no timeout or timeout of 2-30 minutes
If you purchased a kit containing the PS24 Power Supply module, you may use
this module to convert one or both VISTA-100 12VDC, 1.7A style Y supervised
bell outputs to 24VFW, 1.7A style Y supervised bell outputs.
UL
1. Burglary bell circuits must be programmed for a timeout of 16 minutes or
longer.
2. Commercial fire alarm systems require bell or indicating circuits to be
supervised.
Bell Circuit Supervision
To supervise bell circuits, do the following:
•
Install a 2K EOL resistor (model 610-7, supplied) across the last notification
appliance on each bell output to be supervised.
•
Program zones 970 (Bell 1) and 971 (Bell 2) for 24-Hr. Trouble response
(zone type 19) (#93 Zone Programming mode).
To unsupervise bell circuits, do the following:
•
Cut the white jumpers W1 (for Bell 1) and/or W4 (for Bell 2) on the main PCB
•
Program zones 970 (Bell 1) and 971 (Bell 2) for a response type of 00 to
disable supervision (#93 Zone Programming mode).
•
Do not
install the EOLR resistor(s) across the unsupervised output(s).
Programming the Bell Outputs
1. Enter Data Field Program mode [Installer Code] + 8 0 0 0.
Program the following data fields:
*08 Temporal Siren Pulse
*13 Select Timeout for Bell 1
*16 Confirmation of Arming Ding for Bell 1
1*47 Enable Chime for Bell 1
3*57 Confirmation of Arming Ding for Bell 2
3*59 Enable Chime for Bell 2
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...