–44–

The system House ID and the Device Address of the receiver are two different
things and need not be the same.   The House ID allows the system to identify
transmitters with a matching House ID.  The Device Address allows the system to
identify the receiver as opposed to other devices connected to its keypad
terminals.  Therefore, the DIP switches on the RF Receiver must match the

Device Address

.  If using 5700 series wireless, the DIP switches on the

transmitters must match the system 

House ID

.

4.

At the "DEVICE ADD?" prompt, press 0 0  

 to exit Menu Mode

programming and return to Data Field programming.  Press  *99 to exit
programming mode or proceed to the next section.

If using a 5800 TM module, it must be programmed for Device Address 28, 29, or
30 (depending on which jumper is cut) as Device Type 1.

House ID Sniffer Mode

This mode applies only to 5700 series systems, or if you are using a wireless
keypad (5827/5827BD in a 5800 series system.

5700 series receivers respond only to transmitters set to the same House ID (01-
31) that is programmed into the control panel.  This prevents system interference
from transmitters in other nearby systems.  Use the House ID Sniffer Mode to
make sure you do not choose a House ID that is in use in a nearby system.  To
enter this mode, proceed as follows:

1.

Enter your "Installer Code" +  #   + 2 .

2.

The receiver will now "sniff" out any House IDs in the area and display them.
Keep the receiver in this mode for about 2 hours to give a good indication of
the House IDs being used. Use a house ID that is  not displayed.

3.

To exit the Sniffer Mode, simply enter your Installer Code + OFF.

4.

If you need to re-program the House ID of the receiver, do so before
proceeding.

Since Sniffer Mode effectively disables RF point reception, Sniffer Mode  cannot
be entered while any partition is armed.

5700 Series Transmitter  Setup

Each 5700 series transmitter has DIP switches to set both the transmitter's zone
number (Transmitter ID)  and the system House ID.  The House I D will be the
same for all transmitters and must match the House ID programmed into the
system for the RF Receiver.  This can be likened to a family in which everyone
has the same last name (House ID), but each person has a different first name
(Transmitter ID).  The zone number must then be programmed into the system
using #93 Menu Mode–Zone Programming Menus.

Transmitter Supervision

• Each transmitter (except 5701 and 5727) is supervised by a check-in signal

that is sent to the receiver at 70-90 minute intervals. If at least one check-in is
not received from a transmitter within a certain period of time (Programmed in
field 1*31), the keypad will display the zone number and "CHECK."

• Each transmitter (including 5701 and 5727) is also supervised for low battery

conditions, and will transmit a low battery signal to the receiver when the
battery has approximately 30 days of life remaining. The keypad will display the
transmitter number and "LO BAT".

Transmitter Battery Life

www.PDF-Zoo.com

firealarmresources.com

Содержание VISTA-100

Страница 1: ...N6019 2 1 96 VISTA 100 COMMERCIAL FIRE AND BURGLARY PARTITIONED SECURITY SYSTEM with SCHEDULING INSTALLATION INSTRUCTIONS and PROGRAMMING GUIDE www PDF Zoo com firealarmresources com ...

Страница 2: ...lway outside may not wake up the sleeper if the door is closed Install a smoke detector inside bedrooms where electrical appliances such as portable heaters air conditioners or humidifiers are used Install a smoke detector at both ends of a hallway if the hallway is more than 40 feet 12 meters long Install smoke detectors in any room where an alarm control is located or in any room where alarm con...

Страница 3: ... Moving from One Page of Programming to Another 16 Viewing Data Fields 16 Entry Errors 16 Programming System Wide Data Fields 17 Programming Partition Specific Data Fields 17 93 Menu Mode Programming 18 Section 5 INSTALLING THE KEYPADS 19 Keypads That May Be Used 19 Wiring To The Keypads 19 Using a Supplementary Power Supply 20 Mounting the Keypads 21 Addressing the Keypads Preliminary Check out P...

Страница 4: ...nsmitters 45 Wireless Zone Assignments for 5700 Series Transmitters 46 Compatible 5700 Series Transmitters 47 5800 Series Transmitter Setup 48 Transmitter Supervision 48 Transmitter Input Types 48 Transmitter Battery Life 48 Compatible 5800 Series Transmitters 49 Programming RF Transmitters 51 Check Out Procedure for Wireless Zones 54 Section 9 RELAY OUTPUTS 55 Relay Basics 55 Wiring the 4204 and ...

Страница 5: ...ke Detector Reset 81 Battery Saver 81 Section 15 DIALER OUTPUTS 82 Section 16 EVENT LOG OPTIONS 84 General Information 84 Event Log Printer Connections 84 Programming Event Log Options 85 Event Logging Procedures 85 Section 17 FINAL POWER UP PROCEDURE 88 Conncecting the AC Transformer 88 Panel Earth Ground Connections 89 Backup Power Calculations 89 Connecting the Backup Battery 90 Total Control P...

Страница 6: ...e 137 Time Windows Definitions Worksheet 138 Programming Time Windows 139 Daily Open Close Worksheet 139 Programming Open Close Schedules 140 Holiday Definitions Schedule Worksheet 141 Programming Holiday Schedules 141 Time Driven Event Worksheet 142 Time Driven Event Programming 144 Limitation of Access by Time Worksheet 146 Access Control Schedules 146 81 Temporary Schedule Menu Mode 147 Program...

Страница 7: ...n 28 KEYPAD FUNCTIONS 171 General Information 171 Arming Functions 171 Arming Functions 171 Global Arming 172 Access Control 173 Delay Closing Time 173 Partition Goto Commands 173 Viewing Capabilities Of A User 173 Viewing Zone Descriptors 174 Viewing Downloaded Messages 174 Using The Built In User s Manual 174 Panic Keys 174 Speed Key D Macros 174 Manual Relay Activation Mode 70 Mode 175 Section ...

Страница 8: ...odules 34 11 5881 RF Receiver cover removed 42 12a 4204 Relay Module Module 56 12b 4204CF Relay Module 56 13 4285 VIP Module Connections 65 14 Audio Alarm Verification Module Connections 69 15 J2 Pin Assignments and Functions 70 16 Remote Keypad Sounder Wiring 71 18 Remote Keyswitch Wiring 72 19a Connections to 7720 Long Range Radio 74 19b Connections to 7720ULF Long Range Radio 74 19c Connections...

Страница 9: ... of these devices Each of the sections covering the installation of peripheral devices includes the programming for that device If you are an experienced user of Ademco products you may choose to wire and then program the entire system at once If so refer to Section 4 Mechanics of Programming and Section 21 Data Field Descriptions after the hardware setup is complete A blank pull out programming f...

Страница 10: ...onal difficulties This symbol indicates a critical note that could seriously affect the operation of the system or could cause damage to the system Please read each warning carefully This symbol also denotes warnings about physical harm to the installer Enter Zn Num 00 Quit 01 Many system options are programmed in an interactive mode by responding to Alpha keypad display prompts These prompts are ...

Страница 11: ...nal Expansion Zones Polling Loop Expansion Supports up to 79 additional hardwire zones using a built in polling multiplex loop interface Current draw can total up to 128mA Polling loop zones have the following characteristics Must use RPM Remote Point Module devices Supervised by control panel Individually assignable to one of 8 partitions Individually assignable to bell outputs and or aux relay W...

Страница 12: ... or Burglary and Panic and or Trouble conditions at all other partitions keypads selectable option Certain system options selectable for each partition such as Entry Exit Delay and Subscriber Account Number User Codes Acccommodates 128 user codes all of which can operate any or all partitions Certain characteristics must be assigned to each user code which are as follows Authority level Master Man...

Страница 13: ... C relay which can be used for one of the following Alarm activation Trouble Supervisory activation 4 wire smoke detector reset Battery saving feature disconnects power from non critical loads 4 hours after AC power loss Optional Output Relays Accommodates the use of 16 relay outputs using ADEMCO s 4204 and 4204CF Relay Modules Each 4204 module provides four Form C relays for general purpose use E...

Страница 14: ... conditions Used with LORRA Long Range Radio equipment or other devices such as a remote keypad sounder keyswitch Armed and Ready LEDs or a printer to print the system s Event Log Event Log Keeps a log of different event types enabled in programming The Event Log has the following characteristics Stores a total of 224 events Can be viewed at the keypad or through the use of V Link software Can be ...

Страница 15: ... that have the automatic test feature Dynamic display of all fire zones that remain untested while test in progress Ability to log results all fire zones tested and untested in system s Event Log Ability to report results all fire zones tested and untested to the central station Built in User s Manual and Descriptor Review For end user convenience the Vista 100 contains a built in Users Manual By ...

Страница 16: ... to one partition can also be assigned to Partition 9 if Master keypad operation is desired see Master Keypad Setup and Operation later in this section Zones Each zone must be assigned to one partition The zones assigned to a partition will be displayed on that partition s keypad s Fire zones must be assigned to Partition 1 Users Each user may be given access to one or more partitions If a user is...

Страница 17: ...arming of the common lobby Two programming fields affect the way the common lobby will react relative to the status of other partitions They are 1 18 Affects Lobby and 1 19 Arms Lobby 1 18 Affects Lobby must be programmed by partition Setting this option to 1 for a specific partition causes that partition to affect the operation of the common lobby as follows a When the first partition that affect...

Страница 18: ...of the other partition when the user takes action Sequence 1 Office 1 Office 2 Lobby Action User 1 Disarms Armed Disarms User 2 Disarmed Disarms No Change User 1 Arms Disarmed No change User 2 Armed Arms Arms Sequence 2 Office 1 Office 2 Lobby Action User 2 Armed Disarms Disarms User 1 Disarms Disarmed No change User 2 Disarmed Arms No Change User 1 Arms Armed No Change Notice that in sequence 1 s...

Страница 19: ...g Remotely If arming or disarming remotely through VLINK downloading software the lobby will not automatically follow another partition that is programmed to arm or disarm the lobby The lobby must be armed separately after arming all affecting partitions first Auto Arming Disarming If scheduling is used to automatically arm and or disarm partitions the Lobby partition will not automatically follow...

Страница 20: ...play that appears at Partition 1 s keypad s Pressing will display FAULT 02 LOADING DOCK WINDOW Additional zone faults will be displayed one at a time To display a new partition s status press Partition No This will display the status of the new partition The Armed LED on a Master keypad will be lit only if all partitions have been armed successfully The Ready LED will be lit only if all partitions...

Страница 21: ...the wiring entry that you will be using DO NOT ATTEMPT TO REMOVE THE KNOCKOUTS AFTER THE CIRCUIT BOARD HAS BEEN INSTALLED Installing The Cabinet Lock Use an Ademco No N6277 Cam Lock and No P3422 2 Clip for universal commercial cabinet 1 Insert the key into the lock Position the lock in the hole making certain that the latch will make contact with the latch bracket when the door is closed 2 While h...

Страница 22: ...inch long Philips head screws supplied after all wiring programming and checkout procedures have been completed CABINET ATTACK RESISTANCE CONSIDERATIONS Shows typical local Grade A listing installation C COM PCB 1 1 RUN BELL WIRES IN CONDUIT PLUG THIS KNOCK OUT CLIP ON DOOR TAMPER SWITCH CABINET MOUNTING HOLE 4 PLACES PLUG THIS KNOCK OUT PLUG THIS KNOCK OUT PLUG THIS KNOCK OUT RUN ALL REMAINING WI...

Страница 23: ...3 Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws Make certain that the mounting screws are tight This insures that there is a good ground connection between the PC board and the cabinet Also dress field wiring away from the microprocessor center section of the PC board Use the 2 loops on the left and right sidewalls of the cabin...

Страница 24: ...ttery standby calculations and battery selection table Panel Earth Ground Connections 1 Connect the earth ground post inside the 1451 enclosure to a good earth ground use grounding methods specified in the National Electric Code Use a green nut supplied to secure the wire to the ground post The earth ground wire should be the only wire under this nut 2 Run a 16AWG wire from this post to the panel ...

Страница 25: ... of many installations These can be changed by the installer to suit specific needs if desired There are four sets of pre programmed communication defaults available including Low Speed 4 2 Express Ademco High Speed and Ademco Contact ID Loading one of these defaults automatically programs industry standard codes that will suit most of your needs These defaults can be changed directly from the 613...

Страница 26: ...fields 1 01 1 76 press 94 to move to 3rd page press 99 to move back to 2nd page third page of fields 2 00 2 21 press 94 to move to 4th page press 99 to move back to 2nd page fourth page of fields 3 00 3 21 Viewing Data Fields To view the contents of a data field press plus the 2 digit field address The field s entries will be displayed but no changes can be made Entry Errors If an address is impro...

Страница 27: ...med First Page of fields 00 90 press 99 or 98 to exit program mode If the number of digits that you enter in a data field is less than the maximum permitted ex phone number the keypad displays the last entry and waits To proceed enter the next data field you wish to program ex press 08 Partition Specific programming fields are skipped unless entered specifically 5 To change to the next page of fie...

Страница 28: ...g Relay Programming Relay Voice Descriptors Custom Index Programming VIP Module substitute words Press 0 NO or 1 YES in response to the displayed menu selection Pressing 0 will display the next choice in sequence The keypad will then prompt you with questions regarding the programming of a particular zone or device Refer to the individual sections to program each option shown The following is a li...

Страница 29: ...eet 18 gauge 1100 feet 16 gauge 1750 feet 1 The length of all wire runs combined must not exceed 2000 feet when unshielded quad conductor cable is used 1000 feet if unshielded cable is run in conduit or if shielded cable is used 2 If more than one keypad is wired to a run then the above maximum lengths must be divided by the number of keypads on the run i e the maximum length would be 225 feet if ...

Страница 30: ...4 AH battery see the POWERING THE SYSTEM section for more information When the control s auxiliary power load for all devices exceeds 1 amp you can power additional keypads from a regulated 12VDC power supply e g Alarm Saf model AS PS5 BFS 12 UL Use a UL Listed battery backed supply for UL installations Connect the additional keypads as shown in Figure 5 using the keypad wire colors shown Be sure ...

Страница 31: ...ads Preliminary Check out Procedure If you want to check that the system is working before connecting field wiring from zones and devices do the following 1 Temporarily connect a 2000 ohm end of line resistor across each of the basic hard wire zones 1 8 as shown in the Summary of Connections diagram Without actual zone wiring or EOL resistors connected the keypads will not display the Ready messag...

Страница 32: ...o the following With at least one two line alpha keypad connected to the system and addressed as described previously 1 Enter data field programming mode Installer code 8 0 0 0 2 Program field 2 00 Number of Partitions Refer to Section 4 MECHANICS OF PROGRAMMING if you need information about how to move around in program mode 3 From Data Field Programming mode press 93 4 Press 0 NO to each menu op...

Страница 33: ... disarming enter 0 Press to continue The screen will prompt for the next keypad address to be programmed 4 Repeat the procedure above for each keypad used in the system 5 When all keypads have been programmed press 00 at this prompt to exit Menu mode programming The following fields are general keypad options you may want to program now They are Partition Specific which means they must be programm...

Страница 34: ...ast device Connect N O devices in parallel across the loop The 2K EOL resistor must be connected across the loop wires at the last device The maximum zone resistance is 100 ohms for zones 1 2 and 8 and 300 ohms for all other zones excluding the 2K EOL resistor Wiring 2 Wire Smoke Detectors to Zones 1 and 2 Zones 1 and 2 have the added capability of supporting 2 wire smoke detectors Each zone provi...

Страница 35: ...tem Sensor 1400 Ionization w B401B base System Sensor 1451 Photoelectric duct detect w DH400 base System Sensor 2451 Ionization duct detector w DH400 base System Sensor 1451DH Ionization direct wire System Sensor 1100 Ionization w B110LP base System Sensor 1151 Photoelectric direct wire System Sensor 2100 Photoelectric w heat sensor direct wire System Sensor 2100T Photoelectric w B110LP base Syste...

Страница 36: ...716B EOL relay module connected as shown 12 VISTA 100 CONTROL PANEL ZONE TERMINALS EOL POWER SUPERVISION RELAY MODULE A77 716B 2000Ω EOLR 4 WIRE SMOKE DETECTORS HEAT DETECTOR 9 10 11 8 7 SHOWN POWERED RELAY OPENS WHEN POWER IS LOST Figure 7 4 Wire Smoke Detector Connections Zones 1 8 2 Connect detectors including heat detectors if used across terminals of the zone selected All detectors must be wi...

Страница 37: ...on is used Program for 24 Hr Audible Alarm zone type 7 when more than one burglary partition is used Enable the Zone 6 Alternate Tamper Function program field 3 17 When set in this manner the zone will trigger a trouble when the panel is disarmed and an alarm when the panel is armed when the zone senses either an open or a short or when an earth ground fault caused by drilling through the AB12 hou...

Страница 38: ...than 3 8 volts Programming Hardwired Zones 1 With at least one two line alpha keypad 6139 6139R wired and set to a proper address 00 30 temporarily apply power to the system 2 Enter data field programming mode Installer Code 8 0 0 0 and program the following data fields 41 EOLR DISABLE FOR ZONES 3 8 1 N C loops 0 EOLR 2 00 NUMBER OF PARTITIONS 1 8 if you haven t already done this in previous secti...

Страница 39: ...y 21 Arm Away 5800 RF only 22 Disarm 5800 RF only 23 No Alarm Response Used for Relay Activation 002 Partition Enter the partition number 1 8 you are assigning this zone to Press to continue 002 Report Code Enter the report code for this zone This screen will appear once for the first digit once for the second and a third time to review a summary of both digits 009 Bell Rly Sel Each zone can be as...

Страница 40: ...resistor across the terminals of unused zones When the DISARMED READY TO ARM message is displayed you can proceed to the next step 4 Fault and then restore every contact or sensor on each zone individually to ensure that it is being monitored by the system Each time a zone is faulted the keypads in the partition to which the zone is assigned should display the number of the faulted zone Tripping f...

Страница 41: ... Point Module devices Supervised by control panel Individually assignable to one of 8 partitions Individually assignable to bell outputs and or aux relay Wiring Addressing RPM Devices All devices on the polling loop must be wired in parallel to the and Polling Loop terminals of the control panel 28 and 29 You can wire from device to device or have multiple branches connected directly to the contro...

Страница 42: ...enter the serial numbers through the keypad or through V Link downloading software all the devices may be connected before powering up to program 3 Note the polling loop devices that have DIP switches on them Set each device s DIP switches for the zone number you are assigning it Refer to the device s instructions or the DIP Switch Tables found at the end of this manual when setting addresses Cert...

Страница 43: ...in series RPM Input Polling Loop Extension Polling Loop RPM RPM RPM Input loop limits 128mA max No more than 64mA on any individual wire run No individual wire run may exceed Gauge Length 22 650 ft 20 950 ft 18 1500 ft 16 2400 ft Total length of all wire runs combined cannot exceed 4000 ft 2000 ft if using unshielded wire in conduit or shielded wire Extension loop limits Same as for the input poll...

Страница 44: ...f all input loops combined 2 Subtract this number from 6400 ft 3200 ft for shielded cable or unshielded cable in conduit The result is the maximum wire run length for each extension loop Figure 10b Polling Loop Connections Using Multiple Extender Modules Polling Loop Supervision A short on the polling loop is indicated by a trouble on its supervisory zone 997 and reports as a trouble condition onl...

Страница 45: ...ay the zone type for the number entered Press to accept entry If a different zone response type is desired enter a different number and press Zone Types are as follows 00 Assign For Unused Zones 01 Entry Exit 1 Burglary 02 Entry Exit 2 Burglary 03 Perimeter Burglary 04 Interior Follower Burglary 05 Trouble By Day Alarm By Night 06 24 Hour Silent Alarm 07 24 Hour Audible Alarm 08 24 Hour Auxiliary ...

Страница 46: ...st fault and three times upon receiving a matching fault signal When the serial number has been successfully learned its number appears in the display A typical display is shown Alternatively the 7 digit serial number can be entered manually through the keypad if printed on the unit itself 009 PROG AS SL 1 A001 3078 1 Press to continue The summary screen will then appear as it did when first enter...

Страница 47: ... of the faulted zone Tripping fire and panic zones will cause external sounders to sound and may trigger the dialer When each zone is restored the READY TO ARM message should appear again If a zone or zones are not displayed at the correct partition s keypad s check both keypad and zone programming to verify the correct partition assignment 5 When you get the proper displays on the keypad s the po...

Страница 48: ... 4278 Quad PIR Quad element PIR with built in RPM connects directly to the polling loop DIP switch programmable Includes mirrors for both wide angle and curtain long range applications Features an auxiliary sensor loop that is non supervised and can accept closed circuit sensors only cannot be used in UL installations 4275 Dual PIR Dual element PIR with built in RPM connects directly to the pollin...

Страница 49: ... products of combustion ionization Smoke Detector detector with built in RPM DIP switch programmable 4939SN BR Serial Number Compact surface mount magnetic reed 4939SN GY Surface Mount contact with built in RPM Reed Contacts Serial number ID learned by control panel 4191SN WH Serial Number Recessed 1 2 dia magnetic reed contact Recessed with built in RPM Reed Contact Serial number ID learned by co...

Страница 50: ...ting of the 5808 smoke detector for commercial fire installations is pending Wireless Systems Available The VISTA 100 supports wireless zones which may be used exclusively or in addition to hardwire and or polling loop zones The system supports two different wireless systems which have many similarities but notable differences in the programming of the transmitters for each system The following re...

Страница 51: ...ay be an indication that the wiring to the receiver is incorrect or that the DIP switches are not set for the same address the receiver was assigned to in the control s Device Programming mode Two identical receivers can be used to provide either a greater area of coverage or to provide redundant protection Any zone from 1 63 can be used as a 5700 series wireless zone Any zone from 1 87 can be use...

Страница 52: ...on procedures regarding antenna mounting etc 4 3 2 1 ON OFF MOUNTING HOLES INTERFERENCE INDICATOR LED CIRCUIT BOARD DIP SWITCH PLUG SOCKET INSERT IN RIGHT HAND TERMINALS ANTENNAS YELLOW RED BLACK GREEN TO CONTROL S REMOTE KEYPAD CONNECTION POINTS EACH RECEIVER MUST BE ON INDIVIDUAL HOME RUN WIRING OPENING KNOCKOUT AREA FOR SURFACE WIRING Figure 11 5881 RF Receiver cover removed 4 Set the receiver ...

Страница 53: ...nstructions Programming The RF Receiver 1 With at least one alpha keypad 6139 6139R wired and set to a proper address 00 30 temporarily apply power to the system 2 Enter data field programming mode Installer Code 8 0 0 0 a If using a 4281 set data field 1 32 to 1 If using a 5881 set data field 1 32 to 2 b Set data field 1 30 RF RCVR CHECK IN INTERVAL 02 15 times 2 3 From data field programming mod...

Страница 54: ...ay them Keep the receiver in this mode for about 2 hours to give a good indication of the House IDs being used Use a house ID that is not displayed 3 To exit the Sniffer Mode simply enter your Installer Code OFF 4 If you need to re program the House ID of the receiver do so before proceeding Since Sniffer Mode effectively disables RF point reception Sniffer Mode cannot be entered while any partiti...

Страница 55: ...al Installing the Transmitters A variety of RF system transmitters can be used to make up the wireless zones These include window door units smoke detectors PIRs and panic buttons Zone number assignments can be from 1 63 1 Set the DIP switches on each 5700 series transmitter to the appropriate zone number and House ID Refer to the Compatible Transmitters Table for zone numbers and programming info...

Страница 56: ...iary 1 through 47 Note that zones 1 63 can be used but have the following limitations 1 Transmitters set for zones 48 55 will transmit once every 12 seconds while the zone is faulted Transmitters set for zones 56 63 will transmit once every 3 seconds while faulted These two ranges of zone numbers could adversely affect transmitter battery life 2 Transmitters set for an ID of 32 through 47 will hav...

Страница 57: ...g glass when a window is broken 5743 Dual Technology 1 63 Detects the sound and shock requires Glassbreak the presence of both to initiate an alarm condition transmission 5775 PIR Detector 32 47 Dual element passive infrared detector with built in selectable pulse count Note There is a 3 minute lock out between fault transmissions to conserve battery life 5727 Wireless Keypad House ID Can be used ...

Страница 58: ...nciate a CHECK condition if covers are removed Transmitter Input Types All of the transmitters described have one or more unique factory assigned input loop codes Each of the inputs requires its own programming zone e g a 5804 s four button inputs require four programming zones Transmitters can be learned as one of the following types Type Description RF Sends periodic check in signals as well as ...

Страница 59: ...attery At the end of the battery s life the entire unit must be replaced If using for arming disarming the button must be assigned to a user code when adding a user 5802MN Miniature UR or RF Has single pushbutton Personal Emergency Usually programmed for a Transmitter response type of 24 Hr Audible or 24 Hr Silent other zone responses are possible If using for arming disarming the button must be a...

Страница 60: ...Features the same built in panic functions as wired keypads The keypad is identified as zone 00 on wired keypads when it transmits with a low battery 5827BD Wireless House ID used with 5800TM Module Bi directional Keypad Operates the system similarly to wired keypads Can indicate system status via its 3 LEDs and sounder Includes 3 panic keys House ID must be set Requires 5800TM Transmitter Module ...

Страница 61: ...ESS KEYPAD ASSIGNMENT if using keypad 1 49 SUPPRESS TX SUPERVISION SOUNDING 1 yes 0 no If using an RF button 5801 5803 etc also program the following fields 1 57 5800RF BUTTON GLOBAL ARM 1 yes 0 no 1 58 5800 RF BUTTON FORCE BYPASS 1 yes 0 no 4 Press 99 to return the the first page of data fields 5 From data field programming mode press 93 to display the ZONE PROG prompt ZONE PROG 1 Yes 0 No Press ...

Страница 62: ... continue 009 Report Code Enter the report code for this zone Press to continue This screen will appear once for the first digit once for the second and a third time to review a summary of both digits 009 Bell Rly Sel Each zone can be assigned to activate either one or both bell outputs and or the system s auxiliary relay Enter one of the following assignments 0 none 1 Bell 1 2 Bell 2 3 Bells 1 2 ...

Страница 63: ...itter again The keypad will beep three times to confirm the second transmission and acceptance into the system The serial number will then be displayed on the keypad A typical display is shown below Alternatively the 7 digit serial number can be entered manually through the keypad if printed on the unit itself 009 PROG AS RF 1 A001 3078 1 Press to continue The summary screen will then appear as it...

Страница 64: ...locations for the transmitters and verifies that the RF transmission has sufficient signal amplitude margin for the installed system 1 Enter the Installer Code and press 5 TEST For multi partition systems make sure all partitions are disarmed before entering this mode 2 Once transmitters are placed in their desired locations and the approximate length of wire to be run to sensors is connected to t...

Страница 65: ...grammed condition The system can also be programmed to activate relays at specific times by using the 80 Scheduling Menu Mode Time Driven Events function Wiring the 4204 and 4204CF Relay Modules 1 Set the 4204 or 4204CF s DIP switches for a device address between 01 15 that is not being used by another device keypads RF receivers etc The relay module will not operate until the device address you h...

Страница 66: ...C NC NC NC EITHER OR BOTH CAN BE USED DATA IN FROM CONTROL GROUND DATA OUT TO CONTROL 12VDC SUPPLIES POWER TO MODULE CIRCUITRY INCLUDING NOTIFICATION APPLIANCE RELAY COILS CURRENT DRAIN AT 12V IS 25 mA 80mA PER ACTIVE OUTPUT YEL BLK GRN RED 4204 RELAY MODULE POLARIZED NOTIFICATION APPLIANCES POWER FOR NOTIFICATION APPLIANCE A NOTIFICATION APPLIANCE B 8 28 VDC OR VFW UP TO 2 4A DEPENDING ON BELL CU...

Страница 67: ...ion of the module is desired enter a response type for the module s corresponding supervisory zone This is equal to 800 Device Address For example if the 4204 is set and programmed as Device Address 03 the module s supervisory zone would be 803 Program this zone for response type 19 24 Hr Trouble or 05 Trouble by Day Alarm by Night in 93 Zone Programming mode Output Programming Options Defined The...

Страница 68: ...IST 1 8 activation of the selected device will START B 1 ZONE TYPE SYSTEM OPERATION ZT If all zones to be used to start the device have the same response type and there are no other zones of this type which are not to activate this device then ZONE TYPE may be used instead of using a ZONE LIST and EVENT to activate the device If a System Operation such as DISARMING or ANY FIRE ALARM is to activate...

Страница 69: ...rogramming Relays later in this section and in the Programming Form 2 PARTITION No P The device s Stop Zone Type System Operation may be limited to an occurrence on one partition 1 8 or any partition 0 Programming Output Devices 1 From data field programming mode press 93 to display the ZONE PROG prompt 2 Press 0 NO to each menu option until the RELAY PROG prompt appears Press 1 YES While in this ...

Страница 70: ...5 Trouble Day Alarm Night 06 24 Hr Silent 07 24 Hr Audible 08 24 Hr Aux 09 Fire Alarm or Trouble 10 Interior w Delay 16 Fire With Verification 17 Fire Waterflow 23 No alarm response for output relay activation such as for access control purposes 18 Fire Supervisory 19 24 Hr Trouble 20 Arming Stay 21 Arming Away 22 Disarming Code Off 31 End of Exit Time 32 Start of Entry Time 33 Any Burglary Alarm ...

Страница 71: ...O The system may have some devices which are not intended to be under end user control such as relays activating fire doors or machinery Enter 1 if the end user will be restricted from accessing this relay group If this is a fire bell it will be restricted automatically Press to continue ECP ADDRESS For relay modules 4204 4204CF enter the actual relay module s address 01 15 as set by its DIP switc...

Страница 72: ...st entered Enter 1 to delete that zone list 001 Delete Zone 0 No 1 Yes Enter 1 to delete one or more zones in that zone list Enter 0 if no changes are necessary If 1 is entered the following screen will appear otherwise the Enter Zone List prompt will reappear 001 Zn to Delete 000 QUIT 000 Enter each zone number to be deleted from the zone list pressing after each number View Zn LIST 00 QUIT 00 Th...

Страница 73: ...ised for connection to control panel annunciated and reported as Zone 804 Detailed operating instructions for phone access to the security system are provided with the VIP Module In addition a Phone Access User s Guide is supplied with the VIP Module for the user of the system Mounting the VIP Module The VIP Module may be mounted in the control cabinet if space is available or if this is not possi...

Страница 74: ...one In Tip green wire of direct connect cord 2 Phone In Ring red wire of direct connect cord 3 Phone Out Tip brown wire of direct connect cord 4 Phone Out Ring gray wire of direct connect cord 5 Ground Earth ground terminal 30 on control 6 Audio Out 1 Future use 7 Audio Out 1 Future use 1 Use an RJ31X jack with the phone cable supplied with the control Use an additional RJ31X jack and a Direct Con...

Страница 75: ...NNECTOR WITH FLYING LEADS TO CONTROL PANEL TERMINALS USED FOR KEYPAD CONNECTIONS PREMISES ANSWERING MACHINE AND PHONES RJ31X JACK INCOMING TELCO LINE TO GND TERMINAL ON CONTROL 4285 TERMINAL ASSIGNMENTS 1 TIP 2 RING PHONE INPUT 3 TIP 4 RING PHONE OUTPUT 5 GROUND 6 7 AUDIO OUT 1 FOR FUTURE USE GRAY GRAY BROWN BROWN GREEN GREEN RED RED VISTA 100 CONTROL JACK RED MAIN DIALER JACK RJ31X JACK CALLER ID...

Страница 76: ...IP module is located Press to accept entry DEVICEADDRESS 01 31 00 QUIT The screen will prompt for the next device number to be programmed Press 00 to exit Device Programming QUIT MENU MODE 1 YES 0 NO Press 1 Y to return to the data field programming mode or 0 to access other menu options 1 When using the VIP module program alpha descriptors for the zones and relays you are using in the system as d...

Страница 77: ... the AAV if at least one of the messages was an alarm report If Contact ID format is selected for the primary phone number the control will send a listen in to follow message event code 606 which signals the 685 rev 4 6 or higher to hold the phone connection for 1 minute Once triggering occurs the control will give up the phone line to the AAV module without breaking connection with the central st...

Страница 78: ... shown in Figure 14 If also using a 4285 VIP Module be sure to follow the corresponding diagram when making connections Programming Audio Alarm Verification Module Options 1 With at least one two line alpha keypad 6139 6139R wired and set to a proper address temporarily apply power to the system 2 Enter data field programming mode Installer Code 8 0 0 0 Program the following data fields 1 60 ZONE ...

Страница 79: ...5 16 VISTA 100 CONTROL JACK RED GREEN GRAY BROWN ZONE 5 ZONE 5 22 23 TO CONTROL GND Notes 1 Remove any EOL resistor from control panel terminals 22 23 if any present 8 CONDUCTOR DOUBLE PLUG CORD SUPPLIED RJ31X JACK BROWN GRAY CALLER ID UNIT 1 2 3 4 5 6 All switches should be off except switch 5 which should be on Figure 14 Audio Alarm Verification Module Connections If the phone plug is disconnect...

Страница 80: ...with this connector The panel does not supervise field wiring connected to this connector Program fields 3 19 3 20 are used to select the functions of INPUT 1 and OUT 1 7 as indicated in Figure 15 When using J2 for LORRA INPUT 1 Pin 9 is supervised by Zone 973 which is used for supervision of the LORRA XMIT OKAY signal Assign a 24 hr zone response type 5 or 19 to this zone 1 2 3 4 5 6 7 8 9 FIELD ...

Страница 81: ...ing alarms If used the following must be programmed 1 Field 15 to assign the keyswitch to a partition 1 8 or 9 to silence fire bell if fire alarm occurs Enter 0 to disable 2 Zone 7 must be assigned a non zero response type 3 Field 3 20 must be set to 1 if it is desired to use J2 OUT 1 5 to operate keyswitch ARMED and READY LEDs if keyswitch provides LEDs 4 40 to enable Open Close report for keyswi...

Страница 82: ...e alarm memory indication and reset 2 wire smoke and glass break detectors if used When field 15 is set to 9 the keyswitch operates as follows A momentary short across Zone 7 will silence alarm bell sounds i e turn off Bell 1 Bell 2 and the aux relay if programmed for alarms only if a fire alarm is present Outputs will re sound automatically if a new fire alarm condition is detected Burglary alarm...

Страница 83: ...n the diagram below It is designed to be mounted into a standard single gang electrical box and installed as follows 1 Pull wires from the panel s J2 connector through an opening in the single gang box and splice these wires to the module s flying leads Solderless splices may be used 2 Mount the module s PC board onto one side of the PC board retainer bracket supplied 3 Slide the PC board retainer...

Страница 84: ...ic alarm triggers remain HIGH until a User Code OFF is entered in all enabled partition s which display these conditions The silent panic duress trigger works the same way except that it is momentary when initiated by duress The fire supervisory and trouble triggers remain HIGH until the underlying faults are corrected and the User Code OFF is entered in all enabled partition s which display these...

Страница 85: ...ON FAULT Figure 19b Connections to 7720ULF Long Range Radio 7920SE RADIO 4142TR CABLE WIRES COLORS FIRE ALARM BURGLARY AUDIBLE PANIC ALARM FIRE SUPERVISORY GROUND 1 2 3 4 5 6 7 8 9 10 TROUBLE SILENT PANIC ALARM ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 FAULT TB1 TB2 NOTES 1 The 7920SE cabinet is at circuit ground potential and must be isolated from earth ground to avoid earth ground faults 2 Enable trigg...

Страница 86: ...t an earth ground fault indication if you use a printer or PC which has a 3 prong grounded power cord If this occurs first verify that pin 1 chassis ground is isolated from pin 7 signal ground on the 4100SM s RS232 connector early production versions of the 4100SM have an unmarked 3 8 long bare wire jumper lying near the pin 1 side of the RS232 connector which must be cut to isolate these pins The...

Страница 87: ...s module to convert one or both VISTA 100 12VDC 1 7A style Y supervised bell outputs to 24VFW 1 7A style Y supervised bell outputs UL 1 Burglary bell circuits must be programmed for a timeout of 16 minutes or longer 2 Commercial fire alarm systems require bell or indicating circuits to be supervised Bell Circuit Supervision To supervise bell circuits do the following Install a 2K EOL resistor mode...

Страница 88: ...ring for open short and earth ground faults You may use any UL listed polarized fire indicating device rated for 10 14 VDC operation on this output Observe polarity when wiring polarized devices Compatible Alarm Indicating Devices Compatible devices are listed below The diagram shows how to make connections to these outputs Model Description System Sensor PA400B beige PA400R red Indoor piezo sound...

Страница 89: ...OTES Disconnect the AB12 s factory wired connection from it s terminal 4 to it s outer box Set field 3 17 to 1 to enable zone 6 tamper function Assign zone 6 to a burglary partition Program it for day trouble night alarm response type 05 when this bell is used by only 1 burg part Program it for 24 hr audible alarm response type 07 when this bell is used by more than 1 burg part All wiring from AB1...

Страница 90: ...activated until User Code 67 is entered This option can be used for elevator recall or ventilator shutdown on fire alarms By default the relay is set to activate on alarm zones 1 8 with no timeout field 3 61 1 This usage might be required for a common fire and burglary alarm strobe indicator 7 8 12 11 ALARM AUX RELAY FACTORY DEFAULTS Activates for zone 1 8 alarms steady alarm output No timeout NOT...

Страница 91: ...2 Battery Saver 3 61 3 When this function is selected the auxiliary relay will normally be activated i e N O and pole contacts will be connected N C contact will be open and will de activate 4 hours after the start of an AC power failure Using this feature non critical loads such as supplementary keypads which do not need to be supported for the full 24 hour battery backup period can be disconnect...

Страница 92: ...40DLM backup dialer Telephone line supervision is required for UL Commercial fire alarm systems when a dual line dialer is used for fire signal transmission Telephone Line Supervision The supervision circuits on both dialer outputs will indicate a fault when the tip ring voltage falls below approx 25 volts 13 volts for the main dialer when the main PCB blue jumper is cut 13 volts for the back up d...

Страница 93: ...will make up to 8 attempts to transmit a report to one or both telephone numbers depending upon the report routing option programmed After the eighth attempt the communicator will hang up and a COMM FAIL will be displayed at the keypad The number of dialer attempts are programmed in field 3 21 default 8 must be restricted to 3 4 or 5 attempts if a secondary phone number is programmed The system wi...

Страница 94: ...LET GRAY YELLOW WHITE RED GREEN BROWN BLUE BLACK 4142TR CABLE 8 7 6 5 4 3 2 1 PWR GND RXD not used not used not used not used DTR BLUE RED WHITE 10 FT CABLE SUPPLIED WITH 4100SM SERIAL PRINTER SET FOR 8 DATA BITS NO PARITY 1 STOP BIT 300 1200 BAUD HARDWARE HANDSHAKE USING DTR SIGNAL USE GENDER CHANGER SUPPLIED WITH 4100SM IF PRINTER HAS DB25 MALE CONNECTOR TO TERM 11 TO TERM 12 TO AUX PWR 1 OUTPUT...

Страница 95: ...ne or out of paper The VISTA 100 will not send printing data to the printer unless the DTR signal is high Programming Event Log Options 1 With at least one alpha keypad 6139 6139R wired and set to a proper address temporarily apply power to the system 2 Enter data field programming mode Installer Code 8 0 0 0 Program the following data fields 1 70 EVENT LOG TYPES 1 enable 0 disable for each type 1...

Страница 96: ... either caused an alarm or have been restored in selected partition CHECK EVENT LOG TYPE CCC UUU Displays time date for zones that have caused a trouble or supervisory condition in selected partition BYPASS EVENT LOG TYPE CCC UUU Displays time date for zones that have been bypassed in selected partition OP CL EVENT LOG TYPE CCC UUU Displays time date and user number for each arming and disarming o...

Страница 97: ...ected Only those events occurring from the time of the CLEAR command will be displayed if RECENT display option is selected Press 0 if event log is not to be cleared at this time If 1 is pressed the following will appear ARE YOU SURE 0 NO 1 YES Press 1 if it is desired to clear the event log Press 0 if event log is not to be cleared SCREEN DEFINITIONS RECENT Events since last CLEAR COMPLETE Displa...

Страница 98: ...rmer as follows 1 Remove the front cover of the enclosure 2 Mount the enclosure to the wall near the VISTA 100 panel The enclosure has 4 mounting holes on its back surface for this purpose 3 Run 120VAC wiring to the enclosure in conduit A dedicated circuit must be used Use wire nuts to splice the 120VAC wires to the transformer s white and black primary leads Connect the earth ground post on the b...

Страница 99: ...ol The battery s capacity must be sized to provide 24 hours UL Central Station Fire or 60 hours UL Remote Station Fire of standby time followed by 5 minutes fire only or 15 minutes fire burglary of alarm time This can be determined as follows 1 If using the polling loop fill out the POLLING LOOP CURRENT DRAW WORKSHEET shown on next page to determine the total current drawn from the polling loop 2 ...

Страница 100: ...ATELY SAME AGE AND STATE OF CHARGE USE CABLES PROVIDED AND OBSERVE POLARITY IT IS RECOMMENDED THAT ALL BATTERIES BE REPLACED AT SAME TIME EVEN IF ONLY ONE BATTERY HAS BECOME WEAK AS LONG AS ONE GOOD BATTERY REMAINS CONNECTED THE ONCE PER 60 SECOND BATTERY TEST WILL NOT DETECT THE DISCONNECTION OF REMAINING BATTERIES Figure 24 Connecting the Backup Batteries to the Control POLLING LOOP CURRENT DRAW...

Страница 101: ...rm Aux Power 2 Output Subtotal connector J4 pin 5 400mA max 400mA max 3 Enter devices connected to bell 1 output calculate alarm currents then add to get bell 1 output current subtotal BELL 1 OUTPUT Total Current Device Model Device Current X of Units Standby Alarm XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX XXXXXX Bell 1 Output Subtotal terminals 3 4 1 7amp max XXXXXX 4 Enter devices connected to b...

Страница 102: ...out the worksheets found in the PS24 s instructions instead The total control panel standby load must be limited to 919mA for 24 hour standby time or 345mA for 60 hour standby time using two 12V 17 2AH batteries connected to the PS24 BATTERY CAPACITY CALCULATION WORKSHEET For burglary installations requiring 4 hour standby time followed by 15 minute alarm time use a 12AH battery to support all loa...

Страница 103: ...r an interior zone is faulted the system will start the entry delay period and will sound the bell s siren s and keypad sounders for the duration of entry delay This gives the user time to re enter the premises and disarm the system before exit error occurs If the user does not re enter the premises and disarm the system the system will bypass the faulted entry exit and or interior zone s The rest...

Страница 104: ... bypassed or has a zone response type set to 0 the cross zoning feature will not apply 3 If an Entry Exit zone is paired with an Interior Follower zone be sure to enter the Entry Exit zone as the first zone of the pair This will ensure that the entry delay time is started before the follower zone is processed 4 a If a relay is programmed to activate on a fault of one of the zones the relay will ac...

Страница 105: ...ary This zone type provides a secondary entry delay whenever the zone is faulted if the panel is armed in the Away and Stay modes When the panel is armed in the Instant or Maximum modes no entry delay is provided Secondary exit delay begins whenever the control is armed regardless of the arming mode selected These delays are programmable This zone type is usually assigned to sensors or contacts on...

Страница 106: ...tripped first NOTE FOR PANIC KEYS Keypad panic zones share the same zone response type for all 8 partitions but panics may be individually enabled for each partition Type 16 Fire With Verification This zone type is used when smoke alarm verification is desired on hardwire and polling loop zones containing only 2 wire or 4 wire smoke detectors An open will initiate a trouble response and a short wi...

Страница 107: ...nd Wireless Receiver not receiving signals 990 1st Wireless Receiver not receiving signals 997 Polling Loop short circuit 991 999 Keypad Panics 995 1 panic A key 996 3 panic C key 999 panic B key Response types for zones are enabled in 93 Menu mode Zone Programming Supervisory zones should be given a response type of either 19 24 Hr Trouble or 05 Trouble by Day Alarm by Night Zone 976 is assigned ...

Страница 108: ...m must be disarmed within this period or an alarm will occur Enter the entry delay time 01 15 times 15 seconds or 00 for no delay up to a maximum delay of 225 seconds entry 15 times 15 seconds for zones assigned to Zone Type 01 10 EXIT DELAY 1 partition specific 03 Exit delay defines the delay period that allows users to leave the premises through a door that has been programmed as an entry exit d...

Страница 109: ... about 2 minutes after actual AC loss Enter 0 if no AC power loss keypad sounding is desired 18 BELL 1 AC POWER LOSS ALARM 0 Enter 1 to sound the external alarm sounders connected to Bell Output 1 after AC power has been out for 4 hours Otherwise enter 0 no alarm Must be 1 for UL Commercial Burglary 19 RANDOMIZE AC LOSS REPORT 0 Selecting this option helps prevent an overload of AC loss messages a...

Страница 110: ...ort be sent if any other type of report was sent since the last test report Enter 0 if test reports are to be sent at the set intervals regardless of whether or not other reports have been sent Must be 0 for UL applications 27 TEST REPORT INTERVAL Enter the test reporting interval in hours 001 999 Enter 000 if no test reporting is desired If a test report is desired enter a test code in 93 REPORT ...

Страница 111: ...Y SUBSCRIBER ACCT partition specific Enter 00 09 B F 11 15 15 15 15 15 Enter a 3 or 4 digit depending on report format primary subscriber account number 00 09 B F 11 15 Each number requires a 2 digit entry so as to allow entry of hexadecimal digits B F If a 3 digit account number is to be used only enter data in the first 3 locations leaving the last one unfilled by entering a 33 PRIMARY PHONE NUM...

Страница 112: ...urglary installations all entries must be 0 38 PREVENT ZONE XXX BYPASS partition specific 00 Entering a zone number 001 087 prevents that zone from being bypassed by the user Enter 00 if this feature is not desired all zones can be bypassed 39 ENABLE OPEN CLOSE REPORT FOR INSTALLER CODE partition specific 0 Enter 1 if open close reporting for the installer is desired Otherwise enter 0 40 OPEN CLOS...

Страница 113: ...hearing one ring followed by nothing will not answer the first call but will ready itself to pick up on the first ring of the next incoming call that is received within 30 seconds the downloader calling again Must be 00 for Commercial Fire UL Commercial Burglary installations 45 PRIMARY FORMAT 0 This field selects the reporting format for use on the primary telephone number Enter the appropriate n...

Страница 114: ... SECONDARY Alm Rst Byp Trbl Opn Cls Low Batt Enter 0 for standard or 1 for expanded reporting for the secondary phone number default is 0 Note Expanded overrides 4 2 format 79 ZONE TYPE RESTORES FOR ZONE TYPES 1 8 1 2 3 4 5 6 7 8 Enter 1 to enable restore reporting for individual zone types Enter 0 if no restore report is desired for a zone type 80 ZONE TYPE RESTORES FOR TYPES 9 10 9 10 Enter 1 to...

Страница 115: ...irst 6 locations leaving the last two unfilled Default 15 15 15 15 Erase the field by entering 90 NOTE This field must be programmed if a secondary phone number is used field 34 This account number can be the same as the primary account number 1 17 LOBBY PARTITION 0 Enter the common lobby partition 1 8 Enter 0 if none 1 18 AFFECTS LOBBY partition specific 0 Enter 1 if this partition affects the co...

Страница 116: ...med and disarmed states Must be 1 for UL 1 29 RF TX LOW BATTERY REPORT ENABLE 0 Enter 1 if a trouble message for RF transmitter low battery conditions is to be sent to the central station Enter 0 if no report for transmitter low battery is desired Note that a trouble message will be sent for a transmitter supervision failure independent of this selection Must be 1 for UL 1 30 RF RCVR SUPERVISION C...

Страница 117: ... call waiting on the first attempt DO NOT enable unless call waiting is being used Otherwise enter 0 1 43 PERMANENT KEYPAD DISPLAY BACKLIGHTING 0 partition specific Enter 1 if it is desired that backlighting for the keypad display remain on at all times Enter 0 if the display should remain unlit unless a key is pressed The backlighting then turns off again after a period of keypad inactivity Note ...

Страница 118: ...ommercial Burglary installations 1 56 50 60 Hz CLOCK SPEED 0 Enter 1 for 50 Hz Standard or 0 for 60 Hz Standard Must be set to 0 for U S Installations this is the default 1 57 ENABLE 5800 RF BUTTON GLOBAL ARM 0 Enter 1 to have the system arm disarm in accordance with the button s user s global arming settings Enter 0 if the button is not to be used to global arm the system however home partition a...

Страница 119: ...umbers 05 10 and 93 Menu Mode Relay Programming command 57 refer to 93 and 80 Menu Mode sections in this manual 1 76 ACCESS CONTROL RELAY partition specific 00 The system can be programmed to provide user activated access control If enabled the assigned relay will pulse for 2 seconds when the user enters his code and presses 0 Enter the relay number 00 16 for the relay that will be used for access...

Страница 120: ... closings occur outside the arm and disarm windows Open reports will also be suppressed during the closing window in order to prevent false alarms if the user arms the system then reenters the premises to retrieve a forgotten item Note that openings and closings are still recorded in the event log Enter 0 if exception reporting is not desired Note This field must be set to 1 if No Opening and No C...

Страница 121: ...ER PARTITIONS partition specific Enter 1 to allow fire alarms that occur on other partitions to be displayed at this partition s keypad s Otherwise enter 0 2 23 DISPLAY BURG PANIC ALARMS 0 OF OTHER PARTITIONS Enter 1 to allow burglary and panic alarms that occur on other partitions to be displayed at this partition s keypad s Otherwise enter 0 2 24 DISPLAY TROUBLES 0 OF OTHER PARTITIONS Enter 1 to...

Страница 122: ...XD DTR Enter 0 if pins are to function as selected in 3 20 3 20 TRIGGER OUTPUTS SELECTION 0 Enter 0 for Long Range Radio outputs Remote Keypad Sounder Enter 1 for limited LORRA outputs Keyswitch LEDs Enter 2 for LORRA fire output only 5140LED connection 3 21 MAX OF DIALER RETRIES 8 Enter the maximum number of retries to each telephone number 1 8 Must be 3 4 or 5 for NFPA72 compliant systems if a s...

Страница 123: ... 3 61 AUX RELAY FUNCTION 1 Select the condition that will trigger the auxiliary relay Options are 0 Trouble supervisory 1 alarm silenced by Code OFF 2 Smoke detector reset 3 Battery save 4 Alarm silenced by Code 67 3 82 ENABLE BURG FEATURES ON PARTITION 1 1 Enter 1 to enable burglary features on partition 1 Enter 0 to disable ARM AWAY STAY INSTANT MAXIMUM TEST and CHIME functions burglary features...

Страница 124: ... Aux relay assignment for zone Input Device Type for zone whether RF polling loop etc Learning serial numbers of 5800 series transmitters serial polling loop devices into the system all other zone characteristics must be pre programmed SERIAL NUMBER PROG 0 No 1 Yes For programming the following Input Device Type for zone whether RF polling loop etc Learning serial numbers of 5800 series transmitte...

Страница 125: ...y Backs up to previous screen 0 Press to answer NO 1 Press to answer YES 00 Escapes from menu mode back into data field programming mode if entered at the first prompt of each main menu option Zone Programming Enter Programming mode Installer Code 8 0 0 0 The following fields should be programmed before beginning 2 00 Number of Partitions 1 32 RF Receiver Type Also before programming wireless zone...

Страница 126: ...6 24 hour silent alarm 07 24 hour audible alarm 08 24 hour auxiliary 09 Fire Without Verification 10 Interior w Delay 16 Fire With Verification 17 Fire Waterflow 18 Fire Supervisory 19 24 Hour Trouble 20 Arm stay for 5800 RF only 21 Arm away for 5800 RF only 22 Disarm for 5800 RF only 23 No alarm response ex relay action 020 PARTITION Enter the partition number 1 8 that this zone is located in 020...

Страница 127: ... RF or polling loop serial number devices are being programmed continue to the next prompt 020 LOOP NUMBER OR 020 LEARN S N 1 YES 0 NO If this is a previously learned sensor the loop number for this zone will appear Press to continue If the sensor s serial number has not been learned the serial number can be learned now by entering 1 or it can be learned later by using the SERIAL NUMBER LEARN mode...

Страница 128: ...urn to the Enter Zone No prompt 010 PROG AS RF 2 A000 5372 2 If a serial number has already been learned for that device a summary prompt will appear displaying the type of device and its serial number Press to continue to the Delete S N prompt DELETE S N 0 No 1 Yes Enter 1 to delete the displayed serial numbered device Enter 0 if this device should not be deleted Input type Input 0 or 3 6 If a se...

Страница 129: ...eport Code Programming or through the Zone Programming mode while entering other zone information In the Vista 100 reports are divided into six categories These categories represent the main menu options found in the Report Code Programming mode Reports and the categories in which they are found are as follows ALARM CODES RESTR SUPV CODES SYSTEM GROUP 1 for groups of 16 zones Zone Alarm Reports Al...

Страница 130: ...r other system report codes enter 0 N and press to continue Restore Supervisory Codes RESTR SUPV CODE 1 YES 0 NO 0 Press 1 Y to enter restore and supervisory codes for zones ENTER ZN FOR GRP 000 QUIT 001 Enter one zone for each group of 16 zones 001 016 017 032 etc ALARM RESTORE GRP 001 016 00 Enter the first digit of the alarm restore report code for this group of zones double digit entry The sec...

Страница 131: ...ter the second digit of the report If the user number is desired as the second digit enter 01 not necessary for Contact ID or High Speed formats Press to continue Enter the rest of the codes in the same manner Other codes in System Group 1 are Opening Disarm System Low Battery Low Battery Restore AC Loss AC Restore Periodic Test Power Cancel Program Tamper Once you have entered these report codes ...

Страница 132: ...report Code If the user number is desired as the second digit enter 01 not necessary for Contact ID or High Speed formats Press to continue Enter the rest of the codes in the same manner Other codes in System Group 2 are Early Close Late Open Late Close Failed to Open Failed to Close Auto Arm Failed Schedule Change Once you have entered these report codes the system will prompt QUIT REPORT MENU 1 ...

Страница 133: ...words can be added to those already in memory Thus when an alarm or trouble occurs in a zone an appropriate description for the location of that zone will be displayed at the keypad A custom installer s message can be programmed for each partition which will be displayed when the system is Ready ex THE PETERSON s 1 To program alpha descriptors enter Programming mode then press 93 to display ZONE P...

Страница 134: ...ress 8 to store the complete descriptor and exit or b Select the first letter of the desired description note that A is already displayed Use the 3 key to advance through the alphabet and the 1 key to go backward Press the 3 key repeatedly until B appears press 1 to go backwards if you happen to pass it then press key 6 to display the first available word beginning with B Press the 3 key repeatedl...

Страница 135: ...vance through the list of symbols numbers and letters Use the 1 key to move back through the list When you have reached the desired character press the 6 key to select it The cursor will then move to the right in position for the next character 5 Repeat step 3 to create the desired custom word or words Use the 4 key to move the cursor to the left if necessary Use the 7 key to enter a blank or to e...

Страница 136: ...he 4 key to move the cursor to the left Key 7 may be used to insert spaces or erase existing characters 2 Create the message For example to replace READY TO ARM with the message SERVICE 424 0177 proceed as follows Press the 6 key to move the cursor to the right and continue until the cursor is positioned over the first location on the second line Press the 3 key to advance through the alphabet to ...

Страница 137: ...TOR 130 MOTHERS 131 MOTION 132 MOTOR 133 MUD 134 NORTH 135 NURSERY 136 OFFICE 137 OIL 138 OPEN 139 OPENING 140 OUTSIDE 141 OVERFLOW 142 OVERHEAD 143 PAINTING 144 PANIC 145 PASSIVE 146 PATIO 147 PERIMETER 148 PHONE 149 PHOTO 150 POINT 151 POLICE 152 POOL 153 POWER 154 QUAD 155 RADIO 156 REAR 157 RECREATION 158 REFRIG 159 REFRIGERATION 160 RF 161 RIGHT 162 ROOM 163 ROOF 164 SAFE 165 SCREEN 166 SENSO...

Страница 138: ...ppear Enter 1 if the unit is a 4204CF If not enter 0 If 1 is entered only relay 1 Output A and relay 3 Output B on each module are able to be programmed for functions This module is usually used to add two additional supervised bell outputs to the system Press to continue CONSOLE PART If device type 1 Alpha Keypad is selected this prompt will appear Enter the addressable device s default partition...

Страница 139: ...the system s settling delay Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression options Relay Voice Descriptors If using the 4285 VIP Module voice descriptors can be programmed for each of the 16 relays used in the system These descriptors will be announced by the voice module when accessing the relays via the 70 relay access mode via telephone Ea...

Страница 140: ...Attic 119 Baby 120 Back 121 Bar 122 Basement 021 Bathroom 051 Battery 053 Bed 092 Bedroom 015 Blower 123 Boiler 124 Bright 162 Building 125 Burglary 039 Call 009 Central 089 Chime 054 Closed 126 Computer 127 Console 066 Daughter s 208 Den 052 Word Index Detector 128 Device 060 Dim 163 Dining 031 Door 016 Down 008 Downstairs 184 Driveway 130 Duct 131 East 132 Eight 077 Eighth 221 Equipment 133 Exit...

Страница 141: ...mber To enter custom words substitutes do the following 1 From data field programming mode press 93 to display the ZONE PROG prompt 2 Press 0 NO to each menu option until the CUSTOM INDEX prompt is displayed CUSTOM INDEX 0 no 1 yes Enter 1 at this prompt CUSTOMWORDNO 00 QUIT Enter the custom word number 01 20 for which a voice substitute is desired Enter 00 to quit this programming mode Press to a...

Страница 142: ...n detail in this section These menus take you step by step through the options Auto Arming The system can automatically arm AWAY mode itself at the end of a pre determined closing arming time window if the system has not been armed manually Auto arming can be delayed three ways by use of the auto arm delay the auto arm warning or by manually extending the closing arming time window with a keypad c...

Страница 143: ...ase user needs to reenter premises after arming or when the system is in alarm Exception This option allows a means of reporting openings and Reports closings by exception sent only if event occurs outside of the predetermined opening closing time windows The system sends missed open close reports if no opening closing occurs by the end of the corresponding window Time Driven By using time windows...

Страница 144: ...indow 2 9am 10am Saturday open window 3 4pm 4 30pm Saturday close window 4 6pm 6 30pm Monday Thurs close window 5 9pm 9 30pm Friday close window Using the 80 Menu Mode described in a later section the installer can program open close schedules by assigning each time window to a day of the week windows are entered as 2 digit entries Mon Tue Wed Thu Fri Sat Sun Hol Op Cl Op Cl Op Cl Op Cl Op Cl Op C...

Страница 145: ...es these reports from being sent to central station if an arm or disarm is done within the expected time window Reports are only sent if the open close occurs outside the assigned time window The system keeps a record of all openings closings in its event log In the event an opening occurs immediately following a closing during the closing window a person who arms the system forgets something and ...

Страница 146: ...ing time 2 07 Auto disarm delay value 2 08 Force arm enable 2 09 Open close reporting by exception 2 10 Restrict disarm only during windows Event driven relay activation options are programmed using the 93 Menu Mode Relay Programming These actions are in response to a programmed action However relay activation can also be time driven and thus be used to initiate a desired action Time driven relay ...

Страница 147: ...les section for detailed procedures Enter 0 to move to the Holidays prompt Holidays 1 Yes 0 No 0 Enter 1 to program holiday schedules Refer to the Holiday Programming section for detailed procedures Enter 0 to move to the Timed Events prompt Timed Events 1 Yes 0 No 0 Enter 1 to program timed events for relay outputs additional schedules or other system functions Refer to the Programming Timed Even...

Страница 148: ...orksheets will help you define time windows and scheduling aspects of this system before programming the time window definitions for this installation Note that time windows can span midnight Time Window Start Time Stop Time Number HH MM HH MM 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Keep this worksheet handy as you will be asked for a given time window number later in this section Time ...

Страница 149: ...hours digit of the start of window entry Enter the desired start of window hour and press The cursor moves to the minutes Enter the desired minutes and press Toggle the AM PM indication by pressing any key 0 9 while the cursor is under the letter A P position Repeat for the end of window time entry When the entry is completed the TIME WINDOW prompt is displayed again Enter the next time window num...

Страница 150: ...ay s opening schedule Enter 00 if no schedule is desired for a particular day As the number is keyed in the actual time that has been stored for that window will be displayed as a programming aid Press the key to accept the entry Mon P1 CL WIND 00 00 00 00 00 Enter the time window number for the displayed day s closing schedule As the number is keyed in the actual time that has been stored for the...

Страница 151: ...o quit the Holiday menus and display the Quit prompt Enter 0 at the Quit prompt to return to the main menu choices and continue programming Enter 1 to quit Scheduling Menu Mode Quit 1 YES 0 NO 0 01 ENTER DATE 00 00 The cursor will be positioned on the tens of months digit Enter the appropriate month then press to proceed to the day field Enter the appropriate day for the holiday and press to accep...

Страница 152: ...lay 04 Relay Close XX minutes set in field 1 74 Relay 05 Relay Close YY seconds set in field 1 75 Relay 06 Relay Group On Relay Group 07 Relay Group Off Relay Group 08 Relay Group Close for 2 seconds Relay Group 09 Relay Group Close XX minutes set in field 1 74 Relay Group 10 Relay Group Close YY seconds set in field 1 75 Relay Group Arm Disarm commands Activation times 1 Beginning 2 End 3 During ...

Страница 153: ...ring time window active period only On at beginning of window off at end This can be used in conjunction with the arm disarm or bypass commands to control a part of the system during the window For example if bypass is selected to activate during the window the zones in the zone list will be bypassed at the beginning of the window and unbypassed at the end of the window 4 Beginning and end of time...

Страница 154: ...es and continue programming Enter 1 to quit Scheduling Menu Mode Quit 1 YES 0 NO 0 01 ACTION none 00 Enter the action code for the desired action for this event number from the list at the left This could be an output command an arming command or any other time driven event Press to accept the entry and display the appropriate action specifier prompt as follows on the next page Action Codes 01 rel...

Страница 155: ...e to continue 01 Active time 0 Enter the activation code number from 1 4 listed below As the number is keyed in the activation time will be displayed The choices are 1 Trigger at the start of the window 2 Trigger at the end of the window 3 Take effect only for the duration of the window 4 Trigger at both the start and the end of the window Example coffee break buzzer Press the key when the desired...

Страница 156: ... appears Access Sched 1 Yes 0 No 0 Enter 1 to program access schedules ACCESS SCHED 01 08 00 Quit 01 Enter the access control schedule number between 01 and 08 Press to accept entry Enter 00 at the Access Sched prompt to quit the Access control menus and display the Quit prompt Enter 0 at the Quit prompt to return to the main menu choices and continue programming Enter 1 to quit Scheduling Menu Mo...

Страница 157: ...rary Schedule which will override the regular open close schedule and the holiday schedule This schedule takes effect as soon as it is programmed and remains active for up to one week Partition Windows Mon Tue Wed Thu Fri Sat Sun 1 Disarm Window Start Time HH MM Stop Time HH MM Arm Window Start Time HH MM Stop Time HH MM 2 Disarm Window Start Time HH MM Stop Time HH MM Arm Window Start Time HH MM ...

Страница 158: ...he minutes are entered in the same manner The AM PM indication is toggled by hitting any key in the 0 9 range while the cursor is under the letter A P position Repeat for the stop time entry Press the key to move to the arming window for Monday Press if no changes are desired Mon ARM WINDOW 00 00AM 00 00AM This prompt asks for the start and end time of arm closing window The cursor will be positio...

Страница 159: ... alpha descriptor The installer may set certain relays to be restricted during 93 Menu Mode Relay Programming These relays may not be controlled by the end user prevents end user from controlling doors pumps etc To enter this mode the user enters Security Code 83 Output Timer 01 20 00 Quit 01 Enter the output timer number to be programmed 01 20 Press to accept entry and move to the next prompt Ent...

Страница 160: ...hat day Pressing 0 will toggle all days on off The outputs will only be in effect for the days which have the letter x underneath them As the week progresses the selected days are reset to the inactive state unless the permanent option is selected next screen prompt When completed press to continue 06 Permanent 0 NO 1 YES 0 Selecting Permanent means that this schedule will be in effect on a contin...

Страница 161: ...o get a valid message through The number of attempts that are made to each number is determined by the programming of field 3 21 If the panel is not successful after its numerous attempts the keypad will display Comm Failure Reporting Formats The following chart defines the three sets of handshake kissoff frequencies that the panel supports and the different formats that can be sent for each FORMA...

Страница 162: ...3 1 4 1 3 1 4 1 4 2 Standard Expanded Low Spd or Express Alarm SSS S A SSS S A SSSS AZ AAA A Z Trouble SSS S T SSS S T SSSS Tt TTT T t Bypass SSS S B SSS S B SSSS Bb BBB B b AC Loss SSS S E SSS S E SSSS EAC EEE E AC Low Batt SSS S L SSS S L SSSS LLB LLL L LB Open SSS S O SSS S O SSSS OU OOO O U Close SSS S C SSS S C SSSS CU CCC C U Test SSS S G SSS S G SSSS Gg GGG G g Restore SSS S R SSS S R SSSS ...

Страница 163: ...bled The status channel might have one of the following conditions 1 DURESS For Duress Plus Channels 9 15 Only 2 OPENING 3 BYPASS For Channels 1 8 Only 4 CLOSING 5 SUPERVISORY TROUBLE For Channels 1 8 Only 6 SYSTEM STATUS AC LOSS in Channel 1 LOW BATTERY in Channel 2 TIME SET in Channel 3 LOG CLEAR in Channel 3 LOG 50 FULL in Channel 3 LOG 90 FULL in Channel 3 LOG OVERFLOW in Channel 3 POWER ON RE...

Страница 164: ... of the following field numbers TABLE OF DEFAULT PROGRAMMING COMMANDS PRESS TO LOAD THIS DEFAULT PROGRAM SET 80 Low Speed communication defaults 81 Ademco 4 2 Express communication defaults 82 Ademco High Speed communication defaults 83 Contact ID communication defaults Loading communication defaults results in the following Low Speed 94 80 Selects low speed standard format with no checksum for bo...

Страница 165: ...M Sensor Tamper 384 RF Transmitter Low Battery Code Definition 401 O C By User 403 Power Up Armed Auto Arm 406 Cancel by User 407 Remote Arm Disarm Download 408 Quick Arm 409 Keyswitch O C 411 Call back Requested 441 Armed STAY 451 Early Open Close 452 Late Open Close 453 Fail to Open 454 Fail to Close 455 Auto arm Fail 457 Exit Error by User 459 Recent Close 521 Bell 1 Bypass 522 Bell 2 Bypass 52...

Страница 166: ...ed 48 LOW SPEED FORMAT Sec 0 49 CHECKSUM VERIFICATION 0 0 No checksum Primary Secondary 50 SESCOA RADIONICS SEL 0 Radionics 51 DUAL REPORTING 0 no 52 STANDARD EXPANDED REPORT FOR PRIMARY 0 0 0 0 0 0 standard Alarm Rstr Bypass Trbl Opn Cls Low Bat 53 STANDARD EXPANDED REPORT FOR SECONDARY 0 0 0 0 0 0 standard Alarm Rstr Bypass Trbl Opn Cls Low Bat COMMUNICATION DEFAULTS for ADEMCO s CONTACT ID FORM...

Страница 167: ...00 036 03 00 03 06 05 00 06 00 037 03 00 03 07 05 00 07 00 038 03 00 03 08 05 00 08 00 039 03 00 03 09 05 00 09 00 040 03 00 04 10 05 00 10 00 041 03 00 04 01 05 00 11 00 042 03 00 04 02 05 00 12 00 043 03 00 04 03 05 00 13 00 044 03 00 04 04 05 00 14 00 045 03 00 04 05 05 00 15 00 046 03 00 04 06 05 00 01 00 047 03 00 04 07 05 00 02 00 048 01 00 04 08 01 00 03 00 049 01 00 04 09 01 00 04 00 050 0...

Страница 168: ...00 087 07 00 08 07 13 00 12 00 601 00 00 00 00 00 00 00 00 602 00 00 00 00 00 00 00 00 603 00 00 00 00 00 00 00 00 604 00 00 00 00 00 00 00 00 605 00 00 00 00 00 00 00 00 606 00 00 00 00 00 00 00 00 607 00 00 00 00 00 00 00 00 608 00 00 00 00 00 00 00 00 609 00 00 00 00 00 00 00 00 610 00 00 00 00 00 00 00 00 611 00 00 00 00 00 00 00 00 612 00 00 00 00 00 00 00 00 613 00 00 00 00 00 00 00 00 614 0...

Страница 169: ... 00 00 00 00 829 00 00 00 00 00 00 00 00 830 00 00 00 00 00 00 00 00 831 00 00 00 00 00 00 00 00 970 00 00 00 00 00 00 00 00 971 03 00 07 01 07 00 02 00 972 03 00 07 02 07 00 03 00 973 03 00 07 03 07 00 04 00 974 03 00 07 04 07 00 05 00 975 00 00 00 00 00 00 00 00 988 00 00 00 00 00 00 00 00 990 00 00 00 00 00 00 00 00 995 00 00 00 00 00 00 00 00 996 00 00 00 00 00 00 00 00 997 07 00 09 07 07 00 0...

Страница 170: ...0 compatible Internal modems must have 4 position DIP switch Modems with 6 position DIP switch will not work 3 Alternatively you may use a 4100SM interface module to direct wire the control panel to your computer at the site 4 V LINK DOWNLOADING software from ADEMCO This software is available on both 3 1 2 and 5 1 4 diskettes and includes a complete User s Manual Getting On Line with a Control Pan...

Страница 171: ...es and reports are disabled during actual uploading or downloading sessions If you are on line but not actively uploading or downloading all alarms will report immediately All other reports will be delayed until you complete the session 2 The keypads remain active when on line with a control but are inactive during actual uploading or downloading sessions On Line Control Functions The following fu...

Страница 172: ...SS Read Only able only to look at the database cannot change any information and cannot see the customer s access codes Part Read Write able to look at and change all information except the customer s access codes Full Read Write able to look at and change any and all information in the database CONTROL COMM ACCESS Read Only able only to Upload and arm the system Not able to DISARM BYPASS or chang...

Страница 173: ...ard see the Summary of Connections diagram on the inside back cover of this manual is intended to be interfaced to either a local serial printer see EVENT LOG PRINTER CONNECTIONS or a computer Make connections to a computer as shown below Note that the violet wire connection for a computer differs from that used when connecting a serial printer 1 2 3 4 5 6 7 8 9 I N P U T 1 G R O U N D O U T 1 O U...

Страница 174: ...ical display shows TIME DATE THU 12 01 AM 01 01 90 2 The day of the week is automatically calculated based on the date entered Time and date entries are made by simply entering the appropriate hour minute month day and year Press the key to accept the entered value The cursor then moves to the right Press the key to move the cursor to the left of the display to the previous position Enter the corr...

Страница 175: ... users can perform most system functions including Test and Chime modes but certain authority levels restrict disarming bypassing or the assigning of other user codes These restrictions are noted in the descriptions below Use the View Capabilities keypad function to view the partitions and authority levels for which a particular user is authorized In highest to lowest ranking these levels are desc...

Страница 176: ...l of 0 1 or 2 May change his own code Open close reporting of added users will be same as his own enabled or disabled as assigned by installer or master Levels 3 5 Operator Codes Can arm and disarm the system to the authority assigned but cannot add or modify any user code May operate a partition with one of the three OPERATOR authority levels A through C listed below Level Title Functions Permitt...

Страница 177: ...ssigned A user levels 0 1 2 only may only ADD users to a LOWER authority level A user may assign other users access to only those partitions to which he himself has access A user can only be DELETED or CHANGED from within the partition he was created in User numbers must be entered as 3 digit entries Single digit user numbers must therefore always be preceded by a 00 example 003 004 005 etc Make s...

Страница 178: ...tions Note that if a user number is already being used in a partition the system will automatically assign an unused User number Also notice that no access is allowed for this user into partitions 3 8 Attempts to access these partitions would be denied automatically To ADD a Master Manager or Operator Code During user code entry normal key depressions at other keypads in a partition will be ignore...

Страница 179: ...l Arm prompts described in the KEYPAD FUNCTIONS section The keypad now prompts for the user s access to the next partition Part 2 SHOP 0 NO 1 YES Press 0 NO or 1 YES depending on whether or not this user will have access to the displayed partition number If NO the keypad displays this prompt for the next partition number in sequence If YES the keypad prompts for the following User s authority leve...

Страница 180: ... or Operator Code Enter your code 8 User number 02 75 your code again Installer Master or Manager code but must be code with higher level of authority than the code being deleted i e Master code can delete a Manager or Operator level code but cannot delete another Master code a Manager code can delete an Operator level code but cannot delete a Master or another Manager code OK TO DELETE 003 0 NO 1...

Страница 181: ...FF key The keypads also feature chime annunciation and 3 panic keys for silent audible fire or personal emergency alarms which can notify the central station of an alarm condition if that service is connected Arming Functions The following is a brief list of system commands For detailed information concerning system functions refer to the User s Manual Display Faulted Before arming the system must...

Страница 182: ...e arming procedure 1 When using the Global Arm feature if there are faults in any of the selected partitions the system will enter a summary mode in which the faulted zones of all of the selected partitions will be displayed These faults must be corrected or bypassed code BYPASS will attempt to bypass the faults in all of the selected partitions This summary mode will end in approx 120 seconds if ...

Страница 183: ...hours This is to prevent the user from deleting the delay after the normal window expires thereby missing the end of the window Partition GOTO Commands Each keypad is assigned a default partition for display purposes and will show only that partition s information To see information for another partition or perform system functions in another partition use the GOTO command code partition number 0 ...

Страница 184: ...iar system procedure The Built in User s Guide is displayed by simply pressing any of the function keys e g OFF AWAY STAY MAXIMUM BYPASS INSTANT CODE TEST READY and CHIME for approximately 5 seconds and then releasing it Abbreviated instructions relative to the key that has been pressed will then be displayed 2 lines of text are displayed at a time This function operates in either the armed or the...

Страница 185: ...e use of the key in a speedkey sequence as its designated function only e g 2 is not interpreted as Arm Away but rather as Enter House ID Sniffer mode Manual Relay Activation Mode 70 Mode The system allows users to manually activate relays by keypad command using either the keypad or a telephone keypad if VIP module is used The user will be prompted either by keypad alpha display or telephone voic...

Страница 186: ...described above Alternatively if 6 seconds elapses with no key depression the voice module will annunciate the ENTER DEVICE CODE NOW message A relay that has been designated as a fire relay is automatically restricted to prevent inadvertant activation deactivation by users Only the Installer Code can override this restriction If the installer attempts to access a fire relay the message RESTRICTED ...

Страница 187: ...test reports to a central station at intervals ranging from once per hour to once per 999 hours field 27 UL requires that a test report be transmitted at least once every 24 hours The VISTA 100 can be programmed to send the first report at any time of the day or at any day of the week after power up field 83 Fire Drill Test code 69 This test causes fire bells or any bell having a non zero response...

Страница 188: ...ls or any bell having a non zero response type in field 3 10 for 3 seconds The system will also send a Start of Walk Test message to the central station and will light all keypad indicators and display window segments to verify that they are working properly The keypads will then display Fire Walk Test in Progress and will sound a single beep every 15 seconds while this test is active The system w...

Страница 189: ...sues a zone 8 glass break detector power reset about 10 seconds after it finds a fault on this zone to allow faulted detectors to be reset To end this test enter any security code and press OFF An end of walk test message will be sent to the central station Armed Burglary System Test 1 Alarm messages will be sent to the central station during the following tests Notify the central station that a t...

Страница 190: ... a numeric display of 6XX where XX 01 16 indicates a trouble on a 4204CF supervised bell output corresponding relay number 01 16 CHECK accompanied by a numeric display of 8XX where XX 00 31 indicates a trouble on a peripheral device connected to the panel s keypad terminals of the corresponding device address 00 31 CHECK accompanied by a numeric display of 9XX where XX 00 99 indicates that a syste...

Страница 191: ...lt for any supervised fire bell Bypass disable of any supervised fire bell Telco fault of either dialer line Bypass disable of of either dialer Earth ground fault present Bypass of earth ground supervisory zone Fault on LORRA XMIT OK signal if enabled LORRA trigger bypassed AC failure Low system battery Keypad supervision fault This report will be sent as follows Contact ID Code 608 High Speed Cha...

Страница 192: ...ermine that the power supply and or backup battery are supplying proper voltages Verify your programming information where applicable Be sure all keypads and devices are addressed properly Note the proper model number of this product and the version level if known along with any documentation that came with the product Note your ADEMCO customer number and or company name Having this information ha...

Страница 193: ...to the VISTA 100 s fire alarm fire supervisory if used and trouble triggers Also connect its XMIT OKAY output to Input 1 on the VISTA 100 s J2 header Program J2 Input 1 system zone 973 for 24 hour trouble response type 19 to send radio faults 4 When the main dialer is used enable it field 3 30 and connect it to a telephone line Assign a 24 hour trouble response type 19 to system zone 974 to enable...

Страница 194: ...ATION BURGLARY ALARM 1 Follow the instructions for UL609 Local installations given above For Grade A Service You must use the VISTA 100 s dialer with a 7720 Long Range Radio Connect the Control s burglary audible panic alarm trigger and trouble trigger on J2 header to the 7720 Program a 24 Hour Trouble response for system zone 974 to enable main dialer supervision The VISTA 100 will activate the b...

Страница 195: ...e Control Panel there is still a problem on the line notify the telephone company that they have a problem and request prompt repair service The user may not under any circumstances in or out of warranty attempt any service or repairs to the system It must be returned to the factory or an authorized service agency for all repairs FCC PART 68 NOTICE This equipment complies with Part 68 of the FCC r...

Страница 196: ... conforme à certaines normes de protection d exploitation et de sécurité des réseaux de télécommunications Le ministère n assure toutefois pas que le matériel fonctionnera à la satisfaction de l utilisateur Avant d installer ce matériel l utilisateur doit s assurer qu il est permis de le raccorder aux installations de l entreprise locale de télécommunications Le matériel doit également être instal...

Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...

Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...

Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...

Страница 200: ... Code Off 1 Bypassing Zones Enter Code Bypass 6 Zone Number To Automatically Bypass All Faulted Zones Use Quick Bypass Quick Bypass Method Enter Code Bypass Chime Mode Enter Code Chime 9 To Turn Chime Mode Off Enter Code Chime Again Partition Goto User Code Partition Number 0 8 GOTO Home Partition User Code 0 Panics 1 Zone 95 A Key Zone 99 B Key 3 Zone 96 C Key View Downloaded Messages Press 0 For...

Страница 201: ...tile Safe and Vault UL611 UL1610 Grades A AA Central Station UL365 Grades A AA Police Connect Fire UL864 NFPA 72 Local Central Station and Remote Station 5140DLM BACKUP DIALER MODULE Physical 2 75 H X 4 W X 1 D Mounts on VISTA 100 main PC board shield using standoffs supplied Misc Connects to VISTA 100 main PC board J3 header using ribbon cable supplied FCC Registration AC398U 62668 MO N 5140LED A...

Страница 202: ...Dip Switch Tables 187 Dip Switches 48 Disable Download Callback 108 Disarm 96 Disarm Delay 133 Disarm Window 147 Disarming 171 Download Command Enables 102 Download Id No 102 Download Phone No 102 Downloaded Messages Viewing 174 Downloader 48 Dual Reporting 104 Duress 165 E ECP Address 61 Enable 5800 RF Button Force Arm 108 Enable 5800 RF Button Global Arm 108 Enable Dialer Reports 104 Enable Forc...

Страница 203: ...dionics Select 104 Sounder Option 23 129 Specifications 191 Standard Expanded Report 104 Start Event 60 Start Time 138 Substitute Word 131 Summary Of Connections 197 Supervised Fire 96 Supervision Pulses For Lorra 111 Supplementary Power Supply 20 Suppress Tx Supervision Sounding 51 108 Swinger Suppression 100 Swinger Suppression 104 System Operation 60 T Tamper Protection 48 Technical Support Con...

Страница 204: ...otion or intrusion that takes place behind walls ceilings floors closed doors glass partitions glass doors or windows Mechanical tampering masking painting or spraying of any material on the mirrors windows or any part of the optical system can reduce their detection ability Passive Infrared Detectors sense changes in temperature however as the ambient temperature of the protected area approaches ...

Страница 205: ...NO CASE SHALL SELLER BE LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER WARRANTY EXPRESS OR IMPLIED OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER EVEN IF THE LOSS OR DAMAGE IS CAUSED BY THE SELLER S OWN NEGLIGENCE OR FAULT Seller does not represent that the products it sells may not be compromised or circumvented that the products will prevent any per...

Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...

Страница 207: ... UP DIALER EARTH GROUND SCREW wire to main PCB terminal 30 J2 VOLTAGE TRIGGERS See instructions for trigger use and programming default functions shown 1 OUT 4 SILENT PANIC DURESS 2 OUT 7 TROUBLE 3 OUT 3 BURGLARY AUDIBLE PANIC 4 OUT 6 SUPERVISORY 5 OUT 2 FIRE 6 OUT 5 REMOTE KEYPAD SOUNDER 7 OUT 1 OPEN CLOSE 8 GROUND 9 IN 1 N O LOOP RATINGS OUT 1 5 7 LOW 2K TO GROUND HIGH 10 14VDC 20mA MAX OTHER OU...

Страница 208: ...N6019 2 6 96 ALARM DEVICE MANUFACTURING CORPORATION A DIVISION OF PITTWAY CORPORATION 165 Eileen Way Syosset New York 11791 Copyright 1996 PITTWAY CORPORATION www PDF Zoo com firealarmresources com ...

Отзывы: