![ADEMCO VISTA-100 Скачать руководство пользователя страница 161](http://html1.mh-extra.com/html/ademco/vista-100/vista-100_installation-instructions-manual_2850251161.webp)
– 151 –
Section 24: SYSTEM COMMUNICATION
This section provides the following information:
• The process of a successful transmission
• An explanation of reporting formats for this system
• Loading communication defaults
• Contact ID report codes
A Successful Transmission
When a control panel calls the central station receiver, it waits to hear a
“handshake ” frequency from the receiver to confirm that the receiver is on-
line and ready to receive its message. Once the panel hears the handshake
it is programmed to listen for, it sends its message. The panel then waits for
a “ kissoff ” frequency from the receiver acknowledging that the message was
received and understood.
Once the handshake frequency is received and understood by the panel, the
panel will send its message. If there is an error in the transmission (the
receiver does not receive a “valid” message), the kissoff frequency will not be
given by the central station receiver.
The panel will make a number of attempts to the primary telephone number
and a number of attempts to the secondary telephone number (if
programmed) to get a valid message through. The number of attempts that
are made to each number is determined by the programming of field 3*21. If
the panel is not successful after its numerous attempts, the keypad will
display “Comm Failure.”
Reporting Formats
The following chart defines the three sets of (handshake/kissoff) frequencies
that the panel supports and the different formats that can be sent for each.
FORMAT
HANDSHAKE
TRANSMITS DATA
KISSOFF
TRANSMIT
TIME
Low Speed
1400Hz
1900Hz (10PPS)
1400Hz
Under 15 secs.
3+1
(Standard
report)
4+1
4+2
Sescoa/Rad
2300Hz
1800Hz (20PPS)
2300Hz
Under 10 secs.
3+1
(Standard
report)
4+1
4+2
Express
1400–2300Hz
DTMF (10 cps)
1400Hz
Under 3 secs.
4+2
High Speed
1400–2300Hz
DTMF (10 cps)
1400Hz
Under 5 secs.
Contact ID
1400–2300Hz
DTMF (10 cps)
1400Hz
Under 3 secs.
ADVISORY: Ademco's Contact ID reporting is capable of uniquely reporting
all 87 zones of information, as well as openings and closings for all 128
users, to central stations equipped with the Ademco 685 receiver using
software level 4.4 or higher. Must be level 4.7 or higher to fully support all
new VISTA-100 report codes. 685 software levels below 4.4 cannot support
Contact ID reporting. If you need to update your 685 receiver, contact your
distributor.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...