REGULATORY AGENCY STATEMENTS
UL INSTALLATION REQUIREMENTS
The following requirements apply to both UL Residential and UL
Commercial Burglary installations:
1. All partitions must be owned and managed by the same person(s).
2. All partitions must be part of one building at one street address.
3. The audible alarm device(s) must be placed where it/they can be heard by
all partitions.
4. The Control cabinet must be protected from unauthorized access. This
can be done by installing a tamper switch on the cabinet door (supplied
with Vista-100) or by installing a UL Listed passive infrared detector
positioned to detect cabinet access. Wire the selected device to any EOLR
supervised zone (zone 1-8). Program this zone for day trouble/night alarm
(type 05) or 24 hour audible alarm (type 07) response. The 24 hour alarm
response must be used for multiple partitioned systems.
5. Remote Downloading and auto-disarming are not UL Listed features.
UL864/NFPA LOCAL FIRE
Configure at least one bell output for supervision and wire polarized fire
alarm indicators to it. Program this bell for temporal sounding.
UL864/NFPA CENTRAL STATION AND REMOTE STATION FIRE
1. Size the back-up battery for 24 hour standby (central station) or 60 hour
standby (remote station) time.
2. For central station service, you may use the 7720ULF or 7920SE
LORRAs alone, the main dialer with a LORRA, or the main dialer with
the 5140DLM back-up dialer module. For remote station service, you
must use the main dialer with the 5140DLM back-up dialer module.
3. When using the LORRA, connect its channel inputs to the VISTA-100's
fire alarm, fire supervisory (if used), and trouble triggers. Also connect
its XMIT OKAY output to Input 1 on the VISTA-100's J2 header.
Program J2 Input 1 system zone 973 for 24 hour trouble response (type
19) to send radio faults.
4. When the main dialer is used, enable it (field (3*30) and connect it to a
telephone line. Assign a 24 hour trouble response (type 19) to system
zone 974 to enable main dialer supervision. The VISTA-100 will activate
the trouble trigger when it detects a main dialer supervision fault.
5. When the back-up dialer is used, install it on the VISTA-100's PCB
shield. Enable it (field (3*30) and connect it to a separate telephone line.
Assign a 24 hour trouble response (type 19) to system zone 975 to enable
back-up dialer supervision.
6. When the dialer is used, program it to send fire alarm, fire supervisory(if
used), trouble, AC loss, low battery, normal dialer test, and off-normal
dialer test reports. Field *27 must be set to "024" maximum so that test
reports are sent at least once every 24 hours.
7. If a secondary number is programmed, set the maximum number of dialer
re-tries to 3, 4, or 5 in field 3*21.
UL609 GRADE A LOCAL MERCANTILE PREMISES/LOCAL
MERCANTILE SAFE & VAULT
1. All zones must be configured for EOLR supervision (*41=0). Wireless
sensors may not be used. If 4190WH RPMs are used, set field *24 to "0"
to enable tamper detection.
2. Attach a door tamper switch (supplied) to the VISTA-100 cabinet
backbox. For safe and vault installations, a shock sensor (not supplied)
must also be attached to the backbox. (Also see MOUNTING THE
CABINET section).
In addition, for safe an d vault applications, a UL Listed contact must be
used inside the cabinet through one of the knockouts for pry-off tamper
purposes.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...