–2–
Supervisory Zones
Provides additional zones for supervision of all peripheral devices such as
keypads, RF Receivers, and relay modules, as well as for system zones (bells,
dialers (telephone lines), earth ground, keypad panics, etc.) and individual relays.
Zone assignments are as follows:
Individual Relay Zones
601-616
Peripheral Device Zones
800-831
System Zones
970-999
(See Section 20:
Zone Index for a full explanation of these zones and specific
zone assignments.)
8 Partitions
Provides the ability to control 8 separate areas independently, each functioning
as if it had its own separate control. Partitioning features include:
•
A "Common Lobby" partition (1-8), which can be programmed to arm
automatically when the last partition that shares the common lobby is
armed and to disarm when the first partition that shares the common
lobby is
disarmed
•
A Master Partition (9), used strictly to assign keypads for the purpose of
viewing the status of all 8 partitions at the same time (master keypads)
•
All zones (except fire) assignable to one of 8 partitions
•
Fire zones must be assigned to Partition 1
•
Keypads assignable to one of 8 partitions or to Master Partition 9 to view
system status
•
Ability to assign Relays to one or all 8 partitions
•
Ability to display Fire and/or Burglary and Panic and/or Trouble
conditions
at all other partitions keypads (selectable option)
•
Certain system options selectable for each partition , such as Entry/Exit
Delay and Subscriber Account Number
User Codes
Acccommodates 128 user codes, all of which can operate any or all partitions.
Certain characteristics must be assigned to each user code, which are as follows:
•
Authority level (Master, Manager, or several other Operator levels)
•
Opening/Closing central station reporting option
•
What partitions the code can operate
•
Global arming capability (ability to arm all partitions the code has access
to
in one command)
•
Use of an RF (button) to arm and disarm the system (RF key must first be
learned into the system
Peripheral Devices
Supports up to 16 addressable devices, which can be any combination of
keypads (6139/6139R), RF receivers (4281/5881), relay modules
(4204/4204CF), and 4285 VIP module. Peripheral Devices have the following
characteristics:
•
Each device set to an individual address (physically) according to the
device's instructions
•
Each device enabled in the system using the Device Programming Mode
(covered later in this manual)
At least one 2-line alpha keypad (6139/6139R) must be connected to the system
for programming (if using keypad programming) and must remain connected to
the system in order to allow the primary user to program additional user codes
into the system at a later time.
Keypad Panic Keys
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA-100
Страница 197: ... 187 Insert DIP Switch Table Board A www PDF Zoo com firealarmresources com ...
Страница 198: ... 188 Insert DIP Switch Table Board B www PDF Zoo com firealarmresources com ...
Страница 199: ... 189 Insert DIP Switch Table Board C www PDF Zoo com firealarmresources com ...
Страница 206: ... 196 NOTES www PDF Zoo com firealarmresources com ...