Settings
Table 133:
TIMERSET Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
t
0.000 - 90000.000
s
0.001
0.000
Delay for settable timer n
3.32.1.8
AND function block
Function block
IEC09000289 V2 EN
Figure 82:
Function block
Functionality
AND and AND20 are used to form general combinatory expressions with Boolean
variables.
The default value in all input is logical TRUE, which makes it possible to use only the
required number of inputs and leave the rest disconnected.
AND has four inputs and AND20 has 20 inputs. The output
OUT
has a default value
FALSE initially, which suppresses one cycle pulse if the function has been put in the
wrong execution order.
Connect at least one output to another function block or to a variable
for the function to execute correctly.
Section 3
1MRS757256 F
Basic functions
148
PML630/Compact Load-Shedding Solution
Technical Manual