Island-parallel status
ISL_PAR_BB1...ISL_PAR_BB4
for busbar 1...4
•
Overload amount
OV_LOAD_BB1...OV_LOAD_BB4
for busbar 1...4
•
Load-shed power
RCV_SR_POW1 and RCV_SR_POW2
for adjacent electrical
areas
•
Spinning reserve status
RCV_SR_STS1
and
RCV_SR_STS2
for adjacent
electrical areas
•
Must shed status
RCV_MS_STS1
and
RCV_MS_STS2
for adjacent electrical
areas
This module receives the network circuit breaker power
POWER_CB
ij
from the
corresponding instances of NCBDCSWI functions.
If
COMP_STS_SRC<n>
is inactive for a power source, the available power for
corresponding power source is zero.
If island-parallel status
ISL_PAR_BB<x>
(x = 1, 2, 3 and 4) is active for any busbar
in a subnetwork, the corresponding subnetwork is considered as in parallel mode else
the subnetwork is considered as in island mode.
Based on the island or parallel mode of the subnetwork and the governor mode of the
generator, the available power of a generator in the corresponding subnetwork is
calculated as shown in
Table 324:
Available power calculation of the generator
Governor mode
Source available power
Island Mode
Parallel Mode
Not applicable
Available power
Available power
Droop
Available power
Active power
MW
Active power
Active power
ISO
Available power
Active power
P-Control
Available power
Available power
Optimize
Available power
Active power
Base load
Active power
Active power
Peak load
Active power
Active power
Based on the subnetwork number of power sources, the module calculates total
available power
AVA_POWER
z
in subnetwork z.
AVA_POWER
z
is the sum of available
power of all power sources in the subnetwork z.
The total active power
ACT_POWER
z
in subnetwork z is the sum of active powers of
the power sources with the subnetwork number z.
Based on the subnetwork number of power source 1 and power source 2, the module
processes the spinning reserve and must-shed received from adjacent electrical areas
for corresponding subnetwork z as follows.
1MRS757256 F
Section 7
Power management functions
PML630/Compact Load-Shedding Solution
287
Technical Manual