Table 364:
Energizing inputs
Description
Value
Rated frequency
50/60 Hz
Operating range
Rated frequency ± 5 Hz
Current inputs
Rated current, I
n
0.1/0.5 A
1)
1/5 A
2)
Thermal withstand capability:
•
Continuously
4 A
20 A
•
For 1 s
100 A
500 A
•
For 10 s
25 A
100 A
Dynamic current withstand:
•
Half-wave value
250 A
1250 A
Input impedance
<100 mΩ
<20 mΩ
Voltage inputs
Rated voltage, U
n
100 V AC/ 110 V AC/ 115 V AC/ 120 V AC
Voltage withstand:
•
Continuous
425 V AC
•
For 10 s
450 V AC
Burden at rated voltage
<0.05 VA
1) Residual current
2) Phase currents or residual current
Table 365:
Binary inputs
Description
Value
Operating range
Maximum input voltage 300 V DC
Rated voltage
24...250 V DC
Current drain
1.6...1.8 mA
Power consumption/input
<0.3 W
Threshold voltage
15...221 V DC (parametrizable in the range in steps
of 1% of the rated voltage)
Threshold accuracy
±3.0%
Ripple in the DC auxiliary voltage
Max 15% of the DC value (at frequency of 100 Hz)
Adjust the binary input threshold voltage correctly. It is recommended
to set the threshold voltage to 70% of the nominal auxiliary voltage.
The factory default is 16 V to ensure the binary inputs’ operation
regardless of the auxiliary voltage used (24, 48, 60, 110, 125, 220 or
250 V DC). However, the default value is not optimal for the higher
auxiliary voltages. The binary input threshold voltage should be set as
high as possible to prevent any inadvertent activation of the binary
inputs due to possible external disturbances. At the same time, the
Section 11
1MRS757256 F
Technical data
362
PML630/Compact Load-Shedding Solution
Technical Manual
Содержание Relion 630 Series
Страница 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 38: ...32 ...
Страница 202: ...196 ...
Страница 322: ...316 ...
Страница 360: ...354 ...
Страница 374: ...368 ...
Страница 376: ...370 ...