![ABB Relion 630 Series Скачать руководство пользователя страница 201](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813201.webp)
5.1.9
Monitored Data
Table 248:
SPVNZBAT Monitored data
Name
Type
Values (Range)
Unit
Description
U_BATT
REAL
-
kV
Service value of the
battery terminal voltage
AL_ULOW
BOOLEAN
0=FALSE
1=TRUE
-
Alarm when voltage has
been below lower limit for
a set time
AL_UHIGH
BOOLEAN
0=FALSE
1=TRUE
-
Alarm when voltage has
exceeded higher limit for
a set time
ST_ULOW
BOOLEAN
0=FALSE
1=TRUE
-
Start signal when battery
voltage drops below
lower limit
ST_UHIGH
BOOLEAN
0=FALSE
1=TRUE
-
Start signal when battery
voltage exceeds upper
limit
5.1.10
Technical data
Table 249:
SPVNZBAT Technical data
Characteristic
Value
Operation accuracy
±1.0% of the set value
Operate time accuracy
±1.0% of the set value or ±40 ms
1MRS757256 F
Section 5
Supervision functions
PML630/Compact Load-Shedding Solution
195
Technical Manual
Содержание Relion 630 Series
Страница 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 38: ...32 ...
Страница 202: ...196 ...
Страница 322: ...316 ...
Страница 360: ...354 ...
Страница 374: ...368 ...
Страница 376: ...370 ...