3.13.6
Settings
Table 45:
TESTMODE Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
TestMode
Off
On
-
-
Off
Test mode in operation (On) or not (Off)
EventDisable
Off
On
-
-
Off
Event disable during testmode
CmdTestBit
Off
On
-
-
Off
Command bit for test required or not
during testmode
3.14
Disturbance record DRRDRE
3.14.1
Disturbance report DRRDRE
3.14.1.1
Function block
DRRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC09000347-1-en.vsd
IEC09000347 V1 EN
Figure 40:
Function block
3.14.1.2
Functionality
Complete and reliable information about disturbances in the primary and/or in the
secondary system together with continuous event-logging is accomplished by the
disturbance report functionality.
Disturbance report DRRDRE, always included in the IED, acquires sampled data of
all selected analog input and binary signals connected to the function block with a
maximum of 40 analog and 64 binary signals.
The Disturbance report functionality is a common name for several functions.
•
Event list
•
Indications
•
Event recorder
•
Trip value recorder
•
Disturbance recorder
Section 3
1MRS757256 F
Basic functions
76
PML630/Compact Load-Shedding Solution
Technical Manual