![ABB Relion 630 Series Скачать руководство пользователя страница 283](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813283.webp)
7.8.2
Function block
LSCACLS
NW_SOURCE
BB1
BB2
BB3
BB4
BB5
BB6
BLOCK
MAN_POW_SN1
MAN_POW_SN2
MAN_POW_SN3
MAN_POW_SN4
MAN_PRIO_SN1
MAN_PRIO_SN2
MAN_PRIO_SN4
MAN_PRIO_SN3
LS_RESET
LS_RESET_SN1
LS_RESET_SN2
LS_RESET_SN3
LS_RESET_SN4
EXT_LS_TRG
MAN_SHD_SN1
MAN_SHD_SN2
MAN_SHD_SN3
MAN_SHD_SN4
MAN_LS_QVAL
NW_CB12
NW_CB13
NW_CB14
NW_CB15
NW_CB16
NW_CB23
NW_CB24
NW_CB25
NW_CB26
NW_CB34
NW_CB35
NW_CB36
NW_CB45
NW_CB46
NW_CB56
FLS_CNT_RST
SNW1
SNW2
SNW3
SNW4
PPLS1
PPLS2
LS_OPERATE
LS_START
FLS_OPERATE
FLS_START
SLS_OPERATE
SLS_START
OPERATE_BB1
OPERATE_BB2
OPERATE_BB3
OPERATE_BB4
OPERATE_BB5
OPERATE_BB6
B_SET_CHANGE
GUID-98A364D2-6D24-4BB9-B5D6-7C479A7AED0F V2 EN
Figure 149:
Function block
7.8.3
Functionality
The contingency based load-shedding function LSCACLS receives the load-shedding
data of power sources, network circuit breakers and sheddable loads from NPMMXU,
NCBDCSWI and LDMMXU. This function also receives the load-shedding data of
the adjacent electrical areas from NPMMXU. This function determines the number of
groups (subnetwork) of connected busbars and identifies power sources, network
circuit breakers, and sheddable loads in respective groups. During contingency, this
function calculates the load shed priority in the subnetworks provided there is shortfall
in power in the corresponding subnetworks.
1MRS757256 F
Section 7
Power management functions
PML630/Compact Load-Shedding Solution
277
Technical Manual