![ABB Relion 630 Series Скачать руководство пользователя страница 134](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813134.webp)
The input of this GOOSE block must be linked in Signal Matrix by
means of a cross to receive the integer values.
The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD, the DATAVALID
output is HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA, the
DATAVALID output is LOW.
3.24.4
Signals
Table 94:
GOOSEINTRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Table 95:
GOOSEINTRCV Output signals
Name
Type
Description
INTOUT
INTEGER
Integer output
DATAVALID
BOOLEAN
Data valid for integer output
COMMVALID
BOOLEAN
Communication valid for integer output
TEST
BOOLEAN
Test output
3.24.5
Settings
Table 96:
GOOSEINTRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On