3.32.1.3
PULSETIMER function block
Function block
PULSETIMER
INPUT
OUT
IEC09000291-1-en.vsd
IEC09000291 V1 EN
Figure 76:
Function block
Functionality
The pulse function can be used, for example for pulse extensions or limiting of
operation of outputs. The PULSETIMER has a settable length.
Signals
Table 121:
PULSETIMER Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Table 122:
PULSETIMER Output signals
Name
Type
Description
OUT
BOOLEAN
Output signal
Settings
Table 123:
PULSETIMER Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
t
0.000 - 90000.000
s
0.001
0.010
Pulse time length
3.32.1.4
Controllable gate function block GATE
Function block
GATE
INPUT
OUT
IEC09000295-1-en.vsd
IEC09000295 V1 EN
Figure 77:
Function block
Functionality
The GATE function block is used for controlling if a signal should pass from the input
to the output or not, depending on setting.
Section 3
1MRS757256 F
Basic functions
144
PML630/Compact Load-Shedding Solution
Technical Manual