Table 153:
GTI Output signals
Name
Type
Description
OUTPUT
BOOLEAN
Binary output
3.32.1.15
Greater than or equal check for real signals GER
Function block
GUID-1D90C1E8-5B94-427A-A19D-69BABBCB34A7 V1 EN
Figure 89:
Function block
Functionality
The function compares the real inputs
REAL_IN1
and
REAL_IN2
and activates the
binary output
OUTPUT
, if
REAL_IN1
is greater than or equal to
REAL_IN2
.
If
REAL_IN1
≥
REAL_IN2
,
OUTPUT
= 1, else
OUTPUT
= 0.
Logic function blocks do not have the hysteresis feature. Oscillating
outputs should be avoided when comparing analog signals that have
very closely varying values.
Signals
Table 154:
GER Input signals
Name
Type
Default
Description
REAL_IN1
REAL
0.0
Real input 1
REAL_IN2
REAL
0.0
Real input 2
Table 155:
GER Output signals
Name
Type
Description
OUTPUT
BOOLEAN
Binary output
3.32.1.16
Greater than or equal check for integer signals GEI
Function block
GUID-4D68CEF6-6160-4D41-8F56-2C87D7B15FDD V1 EN
Figure 90:
Function block
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
155
Technical Manual