![ABB Relion 630 Series Скачать руководство пользователя страница 133](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813133.webp)
Table 92:
GOOSEDPRCV Output signals
Name
Type
Description
DPOUT
INTEGER
Double point output
DATAVALID
BOOLEAN
Data valid for double point output
COMMVALID
BOOLEAN
Communication valid for double point output
TEST
BOOLEAN
Test output
3.23.5
Settings
Table 93:
GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
3.24
GOOSE function block to receive an integer value
GOOSEINTRCV
3.24.1
Function block
IEC10000250-1-en.vsd
GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250 V1 EN
Figure 66:
Function block
3.24.2
Functionality
GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via
GOOSE.
3.24.3
Operation principle
The DATAVALID output is HIGH if the incoming message is with valid data.
The COMMVALID output becomes LOW when the sending IED is under total failure
condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
127
Technical Manual
Содержание Relion 630 Series
Страница 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 38: ...32 ...
Страница 202: ...196 ...
Страница 322: ...316 ...
Страница 360: ...354 ...
Страница 374: ...368 ...
Страница 376: ...370 ...