Based on the
Ov Curr Trg interval
setting, overcurrent operating statuses of the power
sources can be configured to re-trigger the slow load trigger.
If the
Ov Curr Trg interval
setting is zero, slow load-shedding trigger remains active
until the overcurrent operating status is activated.
If the overcurrent status is activated, slow load-shedding trigger is calculated at an
interval of
Ov Curr Trg interval
load-shedding trigger if
OC_ORP_SRC1
gets activated for power source 1.
OC_OPR_SRC1
t
0
SLS_TRG_SRC1
1
0
1
Time( in seconds)
GUID-2C90BD8E-EF2B-4375-8814-FF68EF4292FD V1 EN
Figure 147:
Profile of slow load trigger w.r.t Ov Curr Trg interval setting
Here, t = Set value of
Ov Curr Trg interval
setting
Figure
shows the calculation of slow load-shedding trigger and slow load-shedding
enable signals for power source 1.
OC_OPR_SRC1
OR
MAX_DMD_SRC1
SLS_TRG_INH
EXT_SLT_SRC1
SLS_INH_SRC1
AND
AND
Slow load shed enable
(To Busbar logic module)
Slow load shed trigger
(To Busbar logic module)
GUID-A787A72E-B271-4CA2-BBE9-3AFD6D4027CA V1 EN
Figure 148:
Logic for calculation of slow load-shedding trigger and slow load-
shedding enable signals for power source 1
The logic is identical for all the power sources.
The module also calculates the slow load-shedding start, fast load-shedding trigger
and busbar number signals for all the power sources.
If the slow load-shedding start signal is activated for any power source (power source
1...power source 8), slow load-shed start
SLS_START
is activated, provided the
SLS_TRG_INH
input is FALSE.
1MRS757256 F
Section 7
Power management functions
PML630/Compact Load-Shedding Solution
269
Technical Manual
Содержание Relion 630 Series
Страница 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 38: ...32 ...
Страница 202: ...196 ...
Страница 322: ...316 ...
Страница 360: ...354 ...
Страница 374: ...368 ...
Страница 376: ...370 ...