7.4.4
Operation principle
The operation of PSCSWI can be described by using a module diagram. All the
modules in the diagram are explained in the next sections.
CB_IED_QVAL
MAX_POWER
POWER
INHIBIT_TRG
CB_SERVICE
CB_LOCK_OUT
IED_TST_MODE
BLK_BYPASS
AP_GOV_QVAL
GOVERNOR_MOD
ACTIVE_POWER
AVA_POWER
GOV_MODE
Compensated
CB status
Block logic
FLS_BLOCK
B_SET_CHANGE
Binary to
integer
Fast load
shed
trigger
logic
ISLAND_PARAL
CB_COMPS_POS
FLS_TRIGGER
Over
current
based load
shed
I_A
I_B
I_C
RESET_OC
EXT_OC_SLST
RESET_DEMAND
ENA_MULT
SLOWLS_OPR
Demand
based load
shed
MAX_DMD_ALM
MAX_CURRENT
OC_STR
OC_OPR
ISLND_PARALL
BB_NUMBER
Slow load
shed logic
DATA_SOURCE
Power
monitoring
General
logic
CB_POSITION
SLS_DISABLE
OVLOD_AMOUNT
SOURCE
INVAL_CRV
GUID-7C8DC2A9-1499-42BF-96CB-2E6F168C6B33 V1 EN
Figure 131:
Functional module diagram
7.4.4.1
Power monitoring
This module calculates the available power and active power of the power source. It
also calculates the governor mode of the generator.
The units of the
POWER
and
MAX_POWER
inputs can be W, kW or MW. This module
converts the units of the
POWER
and
MAX_POWER
inputs in kW as the
Power
convention
setting.
The
POWER
and
MAX_POWER
inputs must have the same unit.
Section 7
1MRS757256 F
Power management functions
216
PML630/Compact Load-Shedding Solution
Technical Manual