Name
Type
Description
B_SET_CHANGE
BOOLEAN
One or many basic settings change
FLS_BLOCK
BOOLEAN
Fast load shed block from network CB
FLS_TRIGGER
BOOLEAN
Fast load shed trigger from network CB
7.6.6
Settings
Table 300:
NCBDCSWI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Block override
No
IED test mode
Quality bad CB
close
Quality bad CB
open
CB Interm or invalid
All yes
-
-
No
Bypass block due to IED test or data
quality or CB position
Table 301:
NCBDCSWI Non group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
CB configuration
Bus coupler
Tie breaker
Virtual Breaker
-
-
Bus coupler
Network CB configuration
CB Pow consider
Sending end IED
Receving end IED
-
-
Sending end IED
CB power to be considered for sending or
receiving end
Snd CB Interm time
0 - 500
ms
10
200
Sending end CB intermediate time
Send Pow convention
Positive W
Negative W
Positive kW
Negative kW
Positive MW
Negative MW
-
-
Positive W
Sending end IED power convention
Rcv CB Interm time
0 - 500
ms
10
200
Receiving end CB intermediate time
Rcv Pow convention
Positive W
Negative W
Positive kW
Negative kW
Positive MW
Negative MW
-
-
Positive W
Receiving end IED power convention
7.6.7
Measured values
Table 302:
NCBDCSWI Measured values
Name
Type
Default
Description
SND_CB_POWER
REAL
0.0
Sending end network CB active power
SND_CB_POS
INTEGER
1
Sending end network CB position
SND_CB_SER
BOOLEAN
1
Sending end network CB service position
Table continues on next page
Section 7
1MRS757256 F
Power management functions
260
PML630/Compact Load-Shedding Solution
Technical Manual