Name
Type
Description
DIF_MUST_ACT
REAL
Difference between the must be load shed and
actual load shed
MAN_SHD_POW
REAL
Manual load shed power settings
MAN_SHD_PRIO
INTEGER
Manual load shed Priority settings
7.10.6
Monitored data
Table 346:
SNWRCLS Monitored data
Name
Type
Values (Range)
Unit
Description
DISABLE_LS
BOOLEAN
0=FALSE
1=TRUE
-
Load shed disable
SN_ACTIVE
BOOLEAN
0=FALSE
1=TRUE
-
Subnetwork active status
LS_BLOCK
BOOLEAN
0=FALSE
1=TRUE
-
Load shed block
SLS_TRG_INH
BOOLEAN
0=FALSE
1=TRUE
-
Slow load shed trigger
inhibit
NEG_POW_BAL
BOOLEAN
0=FALSE
1=TRUE
-
Negative power balance
status
LS_RESET
BOOLEAN
0=FALSE
1=TRUE
-
Load shed reset
MAN_LS_TRG
BOOLEAN
0=FALSE
1=TRUE
-
Manual load shed trigger
LS_OPERATE
BOOLEAN
0=FALSE
1=TRUE
-
Load shed operate
LS_OPR_STS
INTEGER
0=No Load shed
1=Fast Load
shed
2=Slow Load
shed
3=Manual Load
shed
4=Plant level
Load shed
5=Extended
Load shed
-
Load shed operated
status
AVA_POWER
REAL
-
kW
Total Available power
RUNNING_LOAD
REAL
-
kW
Total load
SHDABL_LOAD
REAL
-
kW
Total sheddable load
POWER_BAL
REAL
-
kW
Power balance in the
subnetwork
EFF_POW_BAL
REAL
-
kW
Effective power balance
in the subnetwork
LOD_MISMATCH
REAL
-
kW
Total load mismatch
MUST_SHD_LOD
REAL
-
kW
Must be load shed
ACT_SHD_LOD
REAL
-
kW
Actually shed load
Table continues on next page
Section 7
1MRS757256 F
Power management functions
310
PML630/Compact Load-Shedding Solution
Technical Manual
Содержание Relion 630 Series
Страница 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 38: ...32 ...
Страница 202: ...196 ...
Страница 322: ...316 ...
Страница 360: ...354 ...
Страница 374: ...368 ...
Страница 376: ...370 ...