Signals
Table 179:
TIMERSETQT Input signals
Name
Type
Default
Description
INPUT
BOOLEAN
0
Input signal
Table 180:
TIMERSETQT Output signals
Name
Type
Description
ON
BOOLEAN
Output signal, pick-up delayed
OFF
BOOLEAN
Output signal, drop-out delayed
Settings
Table 181:
TIMERSETQT Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off/On
t
0.000 - 90000.000
s
0.001
0.000
Delay for settable timer n
3.32.2.6
ANDQT function block
Function block
ANDQT
INPUT1
INPUT2
INPUT3
INPUT4
OUT
NOUT
IEC09000297-1-en.vsd
IEC09000297 V1 EN
Figure 103:
Function block
Functionality
ANDQT function is used to form general combinatory expressions with Boolean
variables. ANDQT function block has four inputs and two outputs.
Default value on all four inputs is logical 1 which makes it possible to use only the
required number of inputs and leave the rest un-connected. The output
OUT
has an
initial default value 0, which suppresses one cycle pulse if the function has been put
in the wrong execution order.
1MRS757256 F
Section 3
Basic functions
PML630/Compact Load-Shedding Solution
165
Technical Manual
Содержание Relion 630 Series
Страница 1: ... RELION 630 SERIES Power Management PML630 Compact Load Shedding Solution Technical Manual ...
Страница 2: ......
Страница 26: ...20 ...
Страница 38: ...32 ...
Страница 202: ...196 ...
Страница 322: ...316 ...
Страница 360: ...354 ...
Страница 374: ...368 ...
Страница 376: ...370 ...