3.17.3
Denial of service, frame rate control for LAN1 port DOSLAN1
3.17.3.1
Function block
DOSLAN1
LINKUP
WARNING
ALARM
IEC09000134-1-en.vsd
IEC09000134 V1 EN
Figure 55:
Function block
3.17.3.2
Signals
Table 74:
DOSLAN1 Output signals
Name
Type
Description
LINKUP
BOOLEAN
Ethernet link status
WARNING
BOOLEAN
Frame rate is higher than normal state
ALARM
BOOLEAN
Frame rate is higher than throttle state
3.17.3.3
Settings
The function does not have any parameters available in LHMI or PCM600.
3.17.3.4
Monitored data
Table 75:
DOSLAN1 Monitored data
Name
Type
Values (Range)
Unit
Description
State
INTEGER
0=Off
1=Normal
2=Throttle
3=DiscardLow
4=DiscardAll
5=StopPoll
-
Frame rate control state
Quota
INTEGER
-
%
Quota level in percent
0-100
IPPackRecNorm
INTEGER
-
-
Number of IP packets
received in normal mode
IPPackRecPoll
INTEGER
-
-
Number of IP packets
received in polled mode
IPPackDisc
INTEGER
-
-
Number of IP packets
discarded
Table continues on next page
Section 3
1MRS757256 F
Basic functions
108
PML630/Compact Load-Shedding Solution
Technical Manual