![ABB Relion 630 Series Скачать руководство пользователя страница 280](http://html.mh-extra.com/html/abb/relion-630-series/relion-630-series_technical-manual_2813280.webp)
Table 317:
The group signals for NW_PPLS2
Signal description
Group signal NW_PPLS2
Load-shed data of adjacent area connected with power
source 2
PPLS2_DATA
Fast load-shed CB blocking status for power source 2
CB_BLK_SRC2
Compensated CB open status for power source 2
CCB_OPN_SRC2
7.7.5
Signals
Table 318:
NPMMXU Input signals
Name
Type
Default
Description
SOURCE1
GROUP
SIGNAL
-
Group signal from power source 1
SOURCE2
GROUP
SIGNAL
-
Group signal from power source 2
SOURCE3
GROUP
SIGNAL
-
Group signal from power source 3
SOURCE4
GROUP
SIGNAL
-
Group signal from power source 4
SOURCE5
GROUP
SIGNAL
-
Group signal from power source 5
SOURCE6
GROUP
SIGNAL
-
Group signal from power source 6
SOURCE7
GROUP
SIGNAL
-
Group signal from power source 7
SOURCE8
GROUP
SIGNAL
-
Group signal from power source 8
SLS_TRG_INH
BOOLEAN
0
Slow load shed trigger inhibit
PPLS1_DATA
INTEGER
0
LS data of electrical area connected with power
source 1
PPLS1_QVAL
BOOLEAN
0
Data quality of electrical area connected with
power source 1
PPLS1_TEST
BOOLEAN
0
Electrical area PML test mode connected with
power source 1
PPLS2_DATA
INTEGER
0
LS data of electrical area connected with power
source 2
PPLS2_QVAL
BOOLEAN
0
Data quality of electrical area connected with
power source 2
PPLS2_TEST
BOOLEAN
0
Electrical area PML test mode connected with
power source 2
TEST
BOOLEAN
0
Test mode behaviour of PML IED
Section 7
1MRS757256 F
Power management functions
274
PML630/Compact Load-Shedding Solution
Technical Manual