Startup Operation
56 FSM4000
D184B140U02
The following table describes the available GSD files:
Number and type of
function blocks
ID number
GSD file name
1 x AI
0x9700
PA139700.gsd
1 x AI; 1 x TOT
0x9740
PA139740.gsd
1 x AI; 2 x TOT;
and all manufacturer-specific
parameters
0x078C ABB_078C.gsd
The manufacturer-specific GSD file ABB_078C can be found on the CD shipped with the
device.
The standard GSD files PA1397xx.gsd are available for download from the Profibus
International homepage: http://www.profibus.com
Important
GSD files ABB_078C and the interface description for PROFIBUS PA can be found on the CD
shipped with the device. This can be re-ordered at any time from ABB at no cost (part no.
D699D002U01).
Pos: 31.17 /Überschriften/1.1/1-spaltig/G - I/Inbetriebnahme von Foundation Fieldbus Geräten @ 2\mod_1150787091437_3101.doc @ 30953
6.5
Commissioning FOUNDATION Fieldbus units
Pos: 31.18 /Inbetriebnahme/Durchfluss/FSM4000/Durchführung der Inbetriebnahme/Inbetriebnahme von FOUNDATION FIELDBUS-Geräten @ 16\mod_1196246119343_3101.doc @ 143335
For units with a FOUNDATION fieldbus, the settings of the DIP switch must be checked prior to
commissioning.
When integrating the unit in a process control system, a DD file (device description) and a CFF
file (common file format) are required. The DD file contains the device description. The CFF file
is required for the segment engineering. The engineering can be undertaken online or offline.
The DIP switches on the unit must be set correctly as follows:
DIP switch 1 must be OFF.
DIP switch 2 must also be OFF. Otherwise, the hardware write protection and the process
control system prevent the unit from recording information.
The FOUNDATION fieldbus interface for the unit is compliant with the standards FF-890/891
and FF-902/90. The transmission signal of the transmitter is designed in accordance with IEC
61158-2.
The device is registered with the FOUNDATION fieldbus. The registration number is: IT 027200.
Registration for the FOUNDATION fieldbus is recorded under manufacturer ID 0x000320 and
unit ID 0x0017.