Pos: 21.12 /Technische Daten / Datenblatt/Durchfluss/FSM4000/Einbaubedingungen/Montage in der Nähe von Pumpen @ 3\mod_1157631958985_3101.doc @ 39844
4.6.7 Installation in the vicinity of pumps
•
For flowmeter primaries that are installed near pumps or other
vibration-causing fixtures, the use of mechanical vibration control
components is mandatory.
G00207
Fig. 22
Pos: 21.13 /Technische Daten / Datenblatt/Durchfluss/FSM4000/Einbaubedingungen/Einbau in Rohrleitungen größerer Nennweiten @ 3\mod_1157632081771_3101.doc @ 39865
4.6.8 Installation in larger size pipelines
Determine the resulting pressure loss when using reduction
pieces (1):
1.
Calculate the diameter ratio d/D.
2.
Determine the flow velocity based on the flow range nomograph
(Fig. 24).
3.
Read the pressure drop on the Y-axis in Fig. 24.
G00213
D
d
8°
1
Fig. 23
1
d
V
Δ
p
D
= Flange reducer
= Inside diameter of the flowmeter
= flow velocity [m/s]
= pressure drop [mbar]
= Inside diameter of the pipeline
Nomograph for pressure drop calculations
For flange transition piece with
α
/2 = 8°
Fig. 24