Parameterization
D184B140U02 FSM4000
79
Submenu/parameter
Value range
Comment
Simulation Mode
Off
Off
On
On/Off function for Simulation mode. Before operation
with flow, a flowrate can be simulated. The output values
correspond to the simulated flowrate entered. The
information ** Q Simulation** is displayed in the lower line
of the display. After completing the simulation, change the
parameter in the Simulation Mode menu to "Off".
Simulation Value
0.0 %
Numeric entry
-130 % - +130 %
Select the simulation value for the display and outputs.
Current and pulse output follow the flowrate value.
Submenu
Diagnosis
Menu available only if the required hardware is available.
Diagnose
Manual
Menu is displayed only with "Manual" diagnostic interval.
Start ?
Yes, exit via C/CE
Yes
→
No
Immediately start manual diagnostic. The measured
values are displayed after a delay of 30 s.
Submenu
Diag. Intervall
Cycle Time
Manual
Manual; 10 s; 60 s;
10 min; 60 min; 6 h;
12 h; 24 h; 7 d
Select the time interval between the individual diagnostic
measurements. For the values for Coil Resistance, Coil
Temperature, Insulation Resistance and Magnetic
Linearity, there are minimum measurement intervals due
to technical measurement intervals:
•
60 seconds for Coil Resistance and Coil Temperature
•
5 minutes for Magnetic Linearity
•
10 minutes for measurement of Insulation Resistance
These times are not undershot independently of the
configured diagnostic cyclic.
Submenu
Alert Setting
In this menu a minimum and maximum limit can be set for
each measurement value at which an alarm will be
activated. In addition, the alarm behavior, if the value falls
below or exceeds the thresholds, can be configured as
warnings, errors or deactivated.
Submenu
Alert Coil Volt
Set the thresholds and alarm behavior for the coil AC
voltage.
Min. Val
0 ... 150
Lower range limit for alarm
1.0 V
Max. value
0 ... 150
Upper range limit for alarm
150 V
Status signal
Defines the alarm behavior
Off
Off, warning, error