Safety
8 FSM4000
D184B140U02
Pos: 6.5 /Sicherheit/Durchfluss/Allgemein/Bestimmungswidrige Verwendung (Durchfluss) @ 0\mod_1129705865785_3101.doc @ 3239
1.3 Improper
use
The following uses of the device are prohibited:
•
Operation as a flexible adapter in piping, e.g., to compensate for pipe offsets, pipe vibrations,
pipe expansions, etc.
•
Use as a climbing aid, e.g., for assembly purposes.
•
Use as a support for external loads, e.g., as a support for pipes, etc.
•
Material gain, e.g., by painting over the name plate or adding parts by welding / soldering.
•
Material loss, e.g., by drilling the housing.
Pos: 6.6 /Sicherheit/Allgemein/Hinweis zur bestimmungswidrigren Verwendung (Wartung/Reparatur) @ 0\mod_1129707002440_3101.doc @ 3240
Repairs, alterations and enhancements or the installation of replacement parts is only
permissible as far as described in the manual. Further actions must be verified with ABB
Automation Products GmbH. Excluded from this are repairs performed by ABB-authorized
specialist shops.
Pos: 6.7 /Sicherheit/Durchfluss/Allgemein/Technische Grenzwerte (Durchfluss) @ 0\mod_1129714966562_3101.doc @ 3251
1.4 Technical
limit
values
The device is designed for use exclusively within the stated values on the model plate and
within the technical limit values specified in the data sheets.
The following technical limit values must be observed:
• The permissible operating pressure (PS) in the permissible temperature (TS) may not
exceed the pressure-temperature ratings.
• The maximum operating temperature may not be exceeded.
• The permitted operating temperature may not be exceeded.
• The housing protection system must be observed.
• The flowmeter sensor may not be operated in the vicinity of powerful electromagnetic fields,
e.g., motors, pumps, transformers, etc. A minimum spacing of approx. 1 m (3.28 ft) should
be maintained. For installation on or to steel parts (e.g., steel brackets), a minimum spacing
of approx. 100 mm (3.94 inch) should be maintained (based on IEC801-2 and IECTC77B).