Parameterization
64 FSM4000
D184B140U02
Submenu/parameter
Value range
Comment
Unit Qmax
l/s
l/s; l/min; l/h; m
3
/s;
m
3
/min; m
3
/h; m
3
/d;
usgps; usgpm;
usgph; usmgd; igps;
igpm; igph; igpd;
bbl/s; bbl/m; bbl/h;
bbl/d; g/s; g/min, g/h;
kg/s;kg/min; kg/h;
kg/d; t/min; t/h; t/d;
lb/s; lb/min; lb/h; lb/d;
ml/s, ml/min
Prog. Unit/s
1)
Prog. Unit/min
1)
Prog. Unit/h
1)
Prog. Unit/d
1)
Select the unit for volume and mass flow. This unit refers
to Qmax DN, Qmax and the instantaneous status, if these
are displayed in engineering units.
For PROFIBUS PA, the following units are also displayed:
en ft
3
/s; ft
3
/min; ft
3
/h; ft
3
/d.
For PROFIBUS PA, the following units are not displayed:
Prog. unit and ml/s.
1)
kgal = Factory setting
Submenu
Prog. Unit
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Unit
name
Text
entry
kgal
Four character name for the user programmable unit.
kgal = Factory setting.
Unit factor
3785.1
Numeric entry
Reference factor for the user-defined units based on
liters; default value in kgal units (factory setting).
Prog. Unit
without
density
Without density
With density
Unit for mass (with density) or volume (without density).
Density
1 g/cm3
Numeric entry
Density range 0.1 ... -5 g/cm3. Mass flowrate for display
and totalization. The density is only considered when
mass flow units are and/or totalizer mass units are
selected.
Submenu
System
data
Submenu
Converter
Submenu
Data
50
Hz
This menu does not appear with an excitation frequency
of 60 Hz or 70 Hz.
Channel
-123
µs
View only
Adjustment value for Channel can be monitored for the
excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
Zero
View
only
0 %
Adjustment value for Zero can be monitored for the
excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
Span
→
V
View
only
91 %
Adjustment value for Span Forward can be monitored for
the excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).
Span
←
R
View
only
-91 %
Adjustment value for Span Reverse can be monitored for
the excitation frequency setting (displayed when an older
sensor 50 Hz has been selected).