Electrical
connection
D184B140U02 FSM4000
41
Pos: 29.20 /Überschriften/1.1/1-spaltig/A - C/Anschlusspläne @ 0\mod_1139844727625_3101.doc @ 3179
5.4
Terminal connection diagrams
Pos: 29.21 /Technische Daten / Datenblatt/Durchfluss/FSM4000/Elektrischer Anschluss/Standard DN10 ... DN1000 (2008-03-20 09:33:44) @ 17\mod_1200932209547_3101.doc @ 153702
Standard DN 10 ... DN 1000 (3/8 ... 40")
S4 transmitter (wall mount housing)
G00595
SE
M1
N
2- 1+
L
M3
51 52 81 82 41 42 31 32
SE
3
3
2
2
1S
1S
3
3A
16
16
2S
2S
7
6
1
1
1
1
1
1
1
2
3
4
5
M1
M3
1
6
7
8
12 13
11
9
11 11 14
15
10
Flowmeter sensor
Fig. 36: Connection diagram: Flowmeter sensor standard DN 10 ... DN 1000 (3/8 ... 40")
1
Functional ground (busbar)
2
Pulse output (see page 46)
3
Contact input (see page 45)
4
Contact output (see page 45)
5
Current output (see page 45)
6
Magnet coil cable:
shielded 2 x 1 mm
2
CE Typ 227 TEC 74
ABB order no. D173D147U01, 10 m included in shipment,
standard
7
Supply power
Potent. voltage: 100 ... 230 V AC, terminals L, N,
Low voltage:
20.4 ...26.4 V AC;
L ow
20.4 ... 31.2 V DC
L
Terminals 1+, 2-,
Frequency:
47 Hz
≤
f
≤
53 Hz; 50 Hz supply power
Frequenc
56 Hz
≤
f
≤
64 Hz; 60 Hz supply power
8
Steel shielding
9
Aluminum foil
10
Yellow
11
Shield
12
Blue
13
Red
14
white
15
Shielded signal cable: ABB order no. D173D025U01, 10 m
included in shipment
Comment:
We recommend that shielded output cables be used with the shields connected to the functional ground at one end.