Parameterization
D184B140U02 FSM4000
73
Pos: 33.10 /Konfiguration, Parametrierung/Durchfluss/FSM4000/Parametrierung/Parameterübersicht FSM4000, Teil 2 @ 16\mod_1196764012578_3101.doc @ 144303
Submenu/parameter
Value range
Comment
Totalizer
→
F
0.0 kg/h
Numeric entry
0 ... 9999999
Display or input the forward totalizer value.
Overflow
←
R
0
Display only
Overflow counter max. 65535. 1 overflow = pulse totalizer
of 9,999,999 units. Resets the display status and
increments the overflow counter by one.
Totalizer
←
R
0
Numeric entry
0 ... 9999999
Display or input the reverse totalizer value.
Totalizer reset
Select ENTER to reset the forward/reverse flow totalizer
and overflow counters.
Overflow Diff.
0
Display only
Display the overflow for the diff. totalizer.
Totalizer Diff.
0.0 kg/h
Numeric entry
0 ... 9999999
Display or input the diff. totalizer value.
Submenu
Current
output
This menu does not appear for the PROFIBUS PA or
FOUNDATION fieldbus.
Current
output
0
-
20
mA
0 - 20 mA, 4 - 20 mA
0 - 10 mA, 2 - 10 mA
Select the current output range.
For HART protocol always 4 - 20 mA.
Iout at Alarm
Low Alarm
Low Alarm
High Alarm
Behavior of the current output during an alarm. Low-
Alarm is available only for current output of 2 - 10 mA and
4 - 20 mA. If error 0 (empty pipe) occurs, the current
output is set to the value programmed for the parameter
"lout during empty pipe" in the submenu "Detector empty
pipe". If error 3 (flowrate > 103%) occurs, "High Alarm" is
always signaled.
Iout Low Alarm
3.60 mA
Numeric entry
Low-Alarm is available only for current output of 2 -10 mA
or 4 - 20 mA. Set the current output value during Low
Alarm condition. No selection available if High Alarm is
selected for the current output selection for lout during
alarm and if the transmitter version is standard and the
current output range is
0 - 20 mA
0 - 10 mA
.
Iout High Alarm
21.80 mA
Numeric entry
Set the current output value during High Alarm condition.
If error 3 (flowrate > 103%) occurs, "High Alarm" is always
signaled. No selection available for current output if Low
Alarm is selected for lout during Alarm.
Error 3 mask
Off
Off, On
Deactivates error 3 (flowrate > 103%), if masking = on
Error 4 mask
Off
Off, On
Deactivates error 4 (ext. zero return), if masking = on