Start-up 71
Starting up ACS380 drives
The ACS380 software automatically sets the relevant parameters
when the fieldbus adapter module is connected to the drive.
Automatic configuration is only minimum configuration, and you
can change these parameters later, e.g., Node address.
Parameter
General setting
20.01 Ext1 commands
Fieldbus A
20.03 Ext1 in1
Not selected
20.04 Ext1 in2
Not selected
22.11 Ext1 speed ref1
FB A ref1
22.22 Constant speed sel1
Not selected
22.23 Constant speed sel2
Not selected
23.11 Ramp sel selection
Acc/Dec time 1
28.11 Ext1 frequency ref1
FB A ref1
28.22 Constant frequency sel1
Not selected
28.23 Constant frequency sel2
Not selected
28.71 Freq ramp set sel
Acc/Dec time 1
31.11 Fault reset selection
DI1
50.01 FB A enable
Enable
50.02 FB A comm loss func
Fault
51.02 Node address
3
51.05 Profile
ABB Drives
52.01 FBA A data in1
SW 16 bit
52.02 FBA A data in 2
Act1 16 bit
53.01 FBA A data out1
CW 16 bit
53.02 FBA A data out2
Ref1 16 bit
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...