54 Start-up
5104 FB PAR 4
(TELEGRAM TYPE)
2
(= PPO2)
1)
Displays the telegram type
selected by the PLC
configuration tool.
5105 FB PAR 5
(PROFILE)
0 (= PROFIdrive)
Selects the Control word
according to the
PROFIdrive profile (speed
control mode).
3018 COMM FAULT
FUNC
3
= LAST SPEED Enables fieldbus
communication fault
monitoring.
3019 COMM FAULT
TIME
3.0 s
Defines the fieldbus
communication break
supervision time.
5401 FBA DATA IN 1
4
(= SW 16bit)
1)
Status word
5402 FBA DATA IN 2
5
(= Act1 16bit)
1)
Actual value 1 (speed)
5403 FBA DATA IN 3
106
2)
Power
5404 FBA DATA IN 4
107
2)
DC bus voltage
5501 FBA DATA OUT 1
1
(= CW 16bit)
1)
Control word
5502 FBA DATA OUT 2
2
(= Ref1 16bit)
1)
Reference 1 (speed)
5503 FBA DATA OUT 3
1202
2)
Constant speed 1
5504 FBA DATA OUT 4
1203
2)
Constant speed 2
5127 FBA PAR
REFRESH
1
= REFRESH
Validates the FPBA-01
configuration parameter
settings.
1001 EXT1 COMMANDS 10
= COMM
Selects the fieldbus
interface as the source of
the start and stop
commands for external
control location 1.
1103 REF1 SELECT
8
= COMM
Selects the fieldbus
reference 1 as the source
for speed reference 1.
Drive parameter
Setting for
ACS355 drives
Description
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...