Communication profiles 105
Status word contents
The table below shows the contents of the Status word for the
PROFIdrive communication profile (PROFIdrive parameter
968
).
The upper case boldface text refers to the states shown in the
state machine on page
Bit
Name
Value STATE/Description
Speed control
mode
Positioning mode
0
RDY_ON
1
READY TO SWITCH ON
0
NOT READY TO SWITCH ON
1
RDY_RUN
1
READY TO OPERATE
0
OFF1 ACTIVE
2
RDY_REF
1
ENABLE OPERATION
0
DISABLE OPERATION
3
TRIPPED
1
FAULT
0
No fault
4
OFF_2_STA
1
OFF2 inactive
0
OFF2 ACTIVE
5
OFF_3_STA
1
OFF3 inactive
0
OFF3 ACTIVE
6
SWC_ON_INH
IB
1
SWITCH-ON INHIBIT ACTIVE
0
SWITCH-ON INHIBIT NOT ACTIVE
7
ALARM
1
Warning/Alarm
0
No Warning/Alarm
8
AT_SETPOINT 1
OPERATING.
Actual value equals
reference value (= is within tolerance
limits).
0
Actual value differs from reference value
(= is outside tolerance limits).
9
REMOTE
1
Drive control location: REMOTE
0
Drive control location: LOCAL
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...