110 Communication profiles
Actual values
Actual values are 16-bit or 32-bit words containing information on
the operation of the drive. The functions to be monitored are
selected with a drive parameter.
Actual values in speed control mode
The scaling of 16-bit actual speed values (ACT or NIST_A) in
hexadecimal (0…4000h) corresponds to 0…100% of speed
scaling value (as defined with a drive parameter).
The scaling of 32-bit actual speed values (NIST_B) in hexadecimal
(0…4000 0000h) corresponds to 0…100% of speed scaling value
(as defined with a drive parameter).
Actual values in positioning mode (ACSM1 only)
For a 32-bit actual position value (XIST_A), the unit and scaling
are defined with drive parameters (for example,
POS UNIT
,
POS2INT SCALE
and
FEED
CONST
).