Start-up 69
53.02 FBA DATA
OUT2
2
(= Ref1 16bit
2)
Reference 1
53.03 FBA DATA
OUT3
3
(= Ref2 16bit
2)
Reference 2
51.27 FBA PAR
REFRESH
REFRESH
Validates the FPBA-01
configuration parameter
settings.
10.01 EXT1 START
FUNC
FBA
Selects the fieldbus interface
as the source of the start and
stop commands for external
control location 1.
10.04 EXT2 START
FUNC
FBA
Selects the fieldbus interface
as the source of the start and
stop commands for external
control location 2.
24.01 SPEED REF1
SEL
FBA REF1
Selects the fieldbus reference
1 as the source for speed
reference 1.
32.02 TORQ REF ADD
SEL
FBA REF2
Selects the fieldbus reference
2 as the source for torque
reference 1.
34.01 EXT1/EXT2 SEL
P.FBA MAIN
CW.15
Enables external control
location 1/2 selection through
the fieldbus only (bit 15 in the
fieldbus Control word).
34.03 EXT1 CTRL
MODE1
Speed
Selects speed control as the
control mode 1 for external
control location 1.
34.05 EXT2 CTRL
MODE1
Torque
Selects torque control as the
control mode 1 for external
control location 2.
1)
Read-only or automatically detected/set
2)
Example
Drive parameter
Setting for
ACSM1 drives
Description
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...