58 Start-up
The start sequence for the parameter example above is given
below.
1604 FAULT RESET SEL
8
= COMM
Selects the fieldbus
interface as the source for
the fault reset signal.
1)
Read-only or automatically detected/set
2)
Example
Control word
Start sequence
47Eh (1150 decimal)
READY TO SWITCH ON
47Fh (1151 decimal)
OPERATING (Speed mode)
C7Fh (3199 decimal)
OPERATING (Torque mode)
Drive parameter
Setting for
ACS355 drives
Description