68 Start-up
The table below gives the recommended drive parameter settings.
Drive parameter
Setting for
ACSM1 drives
Description
50.01 FBA ENABLE
Enable
Enables communication
between the drive and the
fieldbus adapter module.
50.02 COMM LOSS
FUNC
Fault
Enables fieldbus
communication fault
monitoring.
50.03 COMM LOSS T
OUT
3.0 s
Defines the fieldbus
communication break
supervision time.
50.04 FBA REF1
MODESEL
Speed
Selects the fieldbus reference
1 scaling.
50.05 FBA REF2
MODESEL
Torque
Selects the fieldbus reference
2 scaling.
51.01 FBA TYPE
PROFIBUS-DP
1)
Displays the type of the
fieldbus adapter module.
51.02 FBA PAR2
(NODE ADDRESS)
3
2)
Defines the PROFIBUS node
address of the fieldbus
adapter module.
51.03 FBA PAR3
(BAUD RATE)
12000
1)
Displays the current baud rate
on the PROFIBUS network in
kbit/s.
51.04 FBA PAR4
(TELEGRAM TYPE)
4
(= PPO4)
1)
Displays the telegram type
selected by the PLC
configuration tool.
51.05 FBA PAR5
(PROFILE)
1 (= ABB
DRIVES)
Selects the Control word
according to the ABB Drives
profile.
52.01 FBA DATA IN1
4
(= SW 16bit)
1)
Status word (PZD 1)
52.02 FBA DATA IN2
5
(= Act1 16bit)
2)
Actual value 1
52.03 FBA DATA IN3
6
(= Act2 16bit)
2)
Actual value 2
53.01 FBA DATA
OUT1
1
(= CW 16bit
1)
Control word
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...