114 Communication profiles
7
ALARM
1
Warning/alarm
0
No warning/alarm
8
AT_SETPOINT 1
OPERATION.
Actual value equals
reference value (= is within tolerance
limits, i.e., in speed control, speed error is
10% maximum of the nominal motor
speed). Note that tolerance limit can be
configured in the drive side, for example,
speed window in this case.
0
Actual value differs from reference (= is
outside tolerance limits).
9
REMOTE
1
Drive control location: REMOTE (EXT1
or EXT2)
0
Drive control location: LOCAL
10
ABOVE_LIMIT
1
Actual frequency or speed equals or
exceeds supervision limit (set by drive
parameter). Valid in both directions of
rotation.
0
Actual frequency or speed within
supervision limit
11
EXT_CTRL_
LOC
1
External Control Location EXT2 selected
0
External Control Location EXT1 selected
12
EXT_RUN_
ENABLE
1
External Run Enable signal received
0
No External Run Enable signal received
13…
14
Drive-specific (For information, see the drive documentation.)
15
FBA_ERROR
1
Communication error detected by
fieldbus adapter module
0
Fieldbus adapter communication OK
Bit
Name
Value STATE/Description
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...