42 Start-up
07
Emul mode
Enables the emulation mode for
the drive. When the mode is
enabled, it is possible to replace a
drive using modules RPBA-01,
NPBA-02 or NPBA-12 in the
PROFIBUS network with a drive
using the FPBA-01 module,
without modifying the PLC
hardware configuration.
The VIK-NAMUR mode enables
the use of ACS880 with the FPBA-
01 module as a VIK-NAMUR
device.
See also
page
0
=
Disabled
0
= Disabled
Emulation mode is disabled.
1
= RPBA-01
RPBA-01 emulation mode is
enabled.
2
= NPBA-02
NPBA-02 emulation mode is
enabled.
3
= NPBA-12
NPBA-12 emulation mode is
enabled.
4
= VIK-NAMUR
VIK-NAMUR emulation mode is
enabled.
08
Map selection
Selects the resolution of parameter
used for PZD mapping through
PROFIdrive parameters 915 and
916.
0 = 32 bit
0
= 32 bit
32 bit scaling
1
= 16 bit
16 bit scaling
09
Module info
Indicates the status of mapping
configuration.
0 = OK
1 =
MAP_ERR_LAST
32 bit parameter is mapped in the
last PZD place
2 =
CFG_ERR_PPO
Wrong PPO/ST type (data size)
code sent by PLC
No. Name/Value
Description
Default
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...