Start-up 55
The start sequence for the parameter example above is given
below.
Speed and torque control using the ABB Drives
communication profile with PPO Type 4
This example shows how to configure a speed and torque control
application that uses the ABB Drives profile. From the PLC
programming point, the ABB Drives profile is similar to the
PROFIdrive profile shown in the first example.
The start/stop commands and reference are according to the ABB
Drives profile. For more information, see section
on page
When Reference 1 (REF1) is used, a reference value of ±20000
(decimal) corresponds to the reference set by parameter
1105
REF1 MAX
in the forward and reverse directions.
When Reference 2 (REF2) is used, a reference value of ±10000
(decimal) corresponds to the reference set by parameter
1108
REF2 MAX
in the forward and reverse directions.
1601 RUN ENABLE
7
= COMM
Selects the fieldbus
interface as the source for
the inverted Run enable
signal (Run disable).
1604 FAULT RESET SEL 8
= COMM
Selects the fieldbus
interface as the source for
the fault reset signal.
1)
Read-only or automatically detected/set
2)
Example
Control word
Start sequence
47Eh (1150 decimal)
READY TO SWITCH ON
47Fh (1151 decimal)
OPERATING (Speed mode)
Drive parameter
Setting for
ACS355 drives
Description
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...