Communication protocol 123
SAP 60 (Slave_Diag)
This SAP gives diagnostic information on the slave station.
Diag_Data
(Diagnostic Data)
Type: Octet String - Length: 6 (Standard)
+ 2 (Extended Diagnosis) (DP-V0 mode)
+ 5 (Extended Diagnosis) (DP-V1 mode)
Note:
During initialization, the module only sends the standard part of the
message.
DU
Byte
Description
0
Station_Status_1
x x x x x x x x
Diag.Station_Non_Existent
(Set by Master, reset by Slave)
Slave not found
Diag.Stagion_Not_Ready
(Set by Slave) Slave not ready for
data exchange
Diag.Cfg_Fault
(Set by Slave)
Received configuration data does
not match original config. data
Diag.Ext_Diag
(Set by Slave)
Diagnostic entry present in slave-
specific diagnostic area
Diag.Not_Supported
(Set by
Slave) Service not supported by
slave
Diag.Invalid_Slave_Response
(Set by Master, reset by Slave)
Invalid response by slave
Diag.Prm_Fault
(Set by Slave)
Invalid parameter or parameter
value
Diag.Master_Lock
(Set by Master, reset by Slave)
Slave is parameterized by
another master
MSB
LSB
Содержание FPBA-01 PROFIBUS DP
Страница 1: ...Options for ABB drives converters and inverters User s manual FPBA 01 PROFIBUS DP adapter module ...
Страница 4: ......
Страница 10: ...10 Table of contents Document library on the Internet 195 ...
Страница 20: ...20 About the manual ...
Страница 26: ...26 Overview of the PROFIBUS network and the FPBA 01 module ...
Страница 30: ...30 Mechanical installation ...
Страница 91: ...Start up 91 8 Click Properties Network Settings and set baud rate ...
Страница 98: ...98 Start up ...
Страница 118: ...118 Communication profiles ...
Страница 178: ...178 Diagnostics ...
Страница 182: ...182 Technical data ...
Страница 190: ...190 Appendix A PROFIdrive parameters ...