Start-up 65
The position set point is scaled as follows:
65.03 POS START 1
C.False
Selects the fieldbus as the
position start1 source.
65.04 POS REF 1 SEL
FBA REF 1
Selects the FBA reference
1 as the position reference
source.
65.11 POS START 2
C.False
Selects the fieldbus as the
position start2 source.
65.22 PROF VEL REF
SEL
FBA REF2
Selects the FBA reference
2 as the velocity reference
source.
66.05 POS ENABLE
C.False
Selects the fieldbus as the
source for enabling the
position reference
generator.
70.03 POS REF ENA
C.False
Selects the fieldbus as the
source for the position
reference enable
command.
1)
Read-only or automatically detected/set
2)
Example
Drive parameter
Setting
60.05 POS UNIT
(Position unit)
m
1)
60.08 POS2INT SCALE
100
1)
1)
Example
Drive parameter
Setting for
ACSM1 drives
Description