14.1.4 Operating instructions / Operation in service
14.1.4.1
Using the Measurement submenus with the PR120/V-PR120/LV
The menu for accessing the functions of the module is illustrated below.
14.1.4.2
Table of submenus for the PR120/V-PR120/LV module
This menu is accessible using the path "Settings/Modules/ PR120/V module"
Parameter / Function
Values
Notes
Rated Voltage
100 V-1000 V
Step 10
Power
Normal
This setting is used to determine the sign of the power
flow *
Reverse
value measured. To check its consistency with the
system, perform the test described in section 13.3.7
*For PR123/DC only.