12.5.5
Modules
When you access the Settings menu, there is a set of menus available relating to the modules.
12.5.5.1
PR120/V-PR120/LV MEASURING module
The primary voltage values can be selected; see section 14.1.
12.5.5.2
PR120/D-M - COM module
The local or remote modes can be selected after entering a password. The serial address can be displayed after entering a password. The Baud
Rate can be set on the values 9600 and 19200 bit/s. The physical protocol provides for the options: (8,E,1), (8,0,1), (8,N,2), (8,N,1). The addressing
can be selected as standard Modbus or ABB. For further information on the PR120/D-M communication module, see paragraph 14.2 in this manual.
12.5.5.3
PR120/K - SIGNALLING module
For a thorough examination of the signalling module, refer to the corresponding section of the module, paragraph 14.3.
12.5.5.4
Settings for the Local Bus unit
If the PR021/K unit is connected, you need to enable the local bus by selecting present.
1/3
Time t1
Thermal memory
L Protection
Threshold I1
eshold I1
1/5
Local
Serial Address
Baudrate
Local / Remote
COM module
12.5.6 Test Menu
Access to the Test menu is password protected.
The menu shows the state of the CB, in the dialog module (COM module) the state of the springs and the position of the CB, and in this submenu
you can make the CB open or close.
Using the "Trip Test" function lets you view the disabling/enabling of the Trip. If it is enabled, the circuit-breaker is opened. The function is only
available with a busbar current of nil (use Vaux, PR030/B or PR010/T).
On the page, only with Vaux, you can also see the state of the circuitbreaker "STATUS", and thus make sure that the input is correctly wired.
4/5
Device test
Settings
Test
Measures
Menu
Password
Enter password
0***
1/6
CB open
Auto Test
Trip Test (disabled)
CB status
Test
Enter
↵
Enter
↵
The surfing path is summarized in the following table:
12.5.6.1
Test Menu table
Parameter / Function
Values
Notes
CB status
Open/Closed/Indefinite
Indefinite in case of fault only
Auto Test
Trip Test
Enabled/Disabled
PR120/D-M
State of springs
Loaded/Unloaded
Module
Position of CB
Isolated/Withdrawn
Open CB
Close CB
PR120/K
Input
ON
Module
Auto Test
- - -
Zone
Protection S
selectivity
(status) Input
ON/OFF
Force Output
Release Output
13.5.7 Information Menu
The Information Menu enables you to view the data relating to the protection unit and the type of circuit-breaker.
1/3
Protection Unit
Nr. :
Version
Normative
Software
G0000A03A
: LSI
: IEC
: P 1.00
Device
: PR122/DC
1/3
Circuit Breaker
Device
Nr. :
Rated Curr.
Installation
Maintenance
: E2B800/SP
: 800 A
: June 12, 2007
: June 12, 2007
AF 050 94 092
1/2
Protection Unit
Circuit Breaker
Protection Unit
About
Enter
↵
ESC +
↓
+ Enter
↵