L3447
Emax DC
91/108
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000635R0002
L3728
15.3 Table showing list of events
15.3.1
"Standard" events for PR120/K and for PR021/K selectable from the relay
Event no.
Description
0.
None
(none enabled)
1.
L prealarm
(L protection prealarm)
2.
L timing
(L protection timing)
3.
S timing
(S protection timing)
4.
L trip
(L protection trip)
5.
S trip
(S protection trip)
6.
I trip
(I protection trip)
7.
G trip
(G protection trip)
8.
Any trip
(tripping of any protection)
9.
Any alarm
(timing of any protection)
10.
Load LC1
(load control LC1 alarm)
11.
Laod LC2
(load control LC2 alarm)
15.3.2 Examples of "Custom" events for the Data Logger function, for PR120/K and PR021/K
No. (decimal)
Event
Notes
PR122
PR123
1920
G timing
-
x
2910
IA, IA2, IB, IB2, sensor error or Trip Coil error
x
x
2688
LC1 alarm
x
x
2049
G alarm
-
x
2306
UV timing
x
x
4124
UV or OV tripped
x
x
33672
CB connected and springs charged
x
x
You can combine the status bits with "and" / "or" logical functions within the same group of events (byte). For more detailed information, refer to
the Modbus Interface document.
15.3.3 "Standard" events for the Data Logger function, selectable from the relay
Event no.
Description
0.
None
(free running)
1.
Any alarm
(any alarm)
2.
L timing
(L protection timing)
3.
Any trip
(tripping of any protection)
15.3.4 Combining the devices needed to customize settings
The "custom" events can be selected using a remote control system, SD-Pocket, or SD-TestBus.
The devices you need to enable you to do so can be selected from among the following:
1) PR122/DC + BT030 + SD-Pocket
2) PR122/DC + PR120/D-M + SD-Testbus or remote system
3) PR122/DC + PR010/T
4) PR123/DC + BT030 + SD-Pocket
5) PR123/DC + PR120/D-M + SD-Testbus or remote system
6) PR123/DC + PR010/T