L3447
Emax DC
55/108
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000635R0002
L3728
L
0.4xIn
≤
I
1
≤
1xIn
3s
≤
t
1
≤
102s
(1)
, step 3s
Release between
± 10%, I
f
≤
4 In
curve IEC60255-3
step 0.01xIn
t1@ 3I
1
1.05 and 1.2xI1
± 20%, I
f
>
4 In
S
1
0.6 xIn
≤
I
2
≤
10xIn
0.05s
≤
t
2
≤
0.35s, step 0.01s
± 7%,I
g
≤
6 In
The best of the two data
(t=k)
step 0.1xIn
0.10s
≤
t
2start-up
≤
30s, step 0.01s
± 10%,I
g
>
6 In
± 10% or 40 ms
0.6 xIn
≤
I
2 start-up
≤
10xIn
0.04s
≤
t
2sel
≤
0.20s, step 0.01s
step 0.1xIn
S
1
0.6xIn
≤
I
2
≤
10xIn
0.05s
≤
t
2
≤
0.35s,
± 7%,I
g
≤
6 In
± 15%, I
g
≤
6 In
(t=k/I
2
)
step 0.1xIn
step 0.01 at 10xIn
± 10%,I
g
>
6 In
± 20%, I
g
>
6 In
S
2
0.6xIn
≤
I
2
≤
10xIn
0.05s
≤
t
2
≤
0.35s, step 0.01s
± 7%,I
g
≤
6 In
The best of the two data
(t=k)
step 0.1xIn
0.10s
≤
t
2start-up
≤
30s, step 0.01s
± 10%,I
g
>
6 In
± 10% or 40 ms
0.04s
≤
t
2sel
≤
0.40s, step 0.005s
I
1,5xIn
≤
I
3
≤
10xIn
≤
30 ms
(t=k)
step 0.1xIn
0.10s
≤
t
2 start-up
≤
30s, step 0.01s ± 10%
where I>I4
MCR
6.0xIn
≤
I
5
≤
10xIn
≤
30 ms
(3)
± 10%
(t=k)
step 0.1xIn
G
(4)
0.20xIn
≤
I
4
≤
1xIn
0.1s
≤
t
4
≤
1s, step 0.05s
The best of the two data
(t=k)
step 0.02xIn
0.1s
≤
t
4start-up
≤
1s, step 0.02s
± 7%
± 10% or 40 ms
0.04s
≤
t
4sel
≤
0.2s, step 0.01s
where I>I4
G
(4)
0.20xIn
≤
I
4
≤
1xIn
0.1s
≤
t
4
≤
1s, step 0.05s
± 7%
± 15%
(t=k/I
2
)
step 0.02xIn @I
g
>4In
U
2%
≤
I
6
≤
90%
0.5s
≤
t
6
≤
60s, step 0.5s
± 10%
The best of the two data
(t=k)
step 1%
± 10% or 40 ms
OT
Fixed,
Instantaneous
± 5°C
_____
(temp=k)
defined by SACE
Iinst
Automatic, defined
Instantaneous
by SACE
UV
0.5xUn
≤
U
8
≤
0.95xUn 0.1s
≤
t
8
≤
5s, step 0.1s
± 5%
The best of the two data
(t=k)
step 0.01xUn
± 10% or 40 ms
OV
1.05xUn
≤
U
9
≤
1.2xUn 0.1s
≤
t
9
≤
5s, step 0.1s
± 5%
The best of the two data
(t=k)
step 0.01xUn
± 10% or 40 ms
RP
- 0.3xPn
≤
P
11
≤
-0.1xPn
0.5s
≤
t
11
≤
25s, step 0.1s
± 10%
The best of the two data
(t=k)
step 0.02 Pn
± 10% or 40 ms
LC1/LC2 loads
50%
÷
100% step 0.05xI
1
control
Warning Iw
0,3
÷
10I
n
step 0,05xI
n
± 10%
10
÷
40 ms
13.2.9.13 Summary table of the protection function settings for the PR123/DC
Protection
Threshold
range
Time
Tolerance
(2)
Time
range
Threshold
tolerance
(2)
Disabling
Disabling
TRIP only
Zone
selectivity
Start-up threshold
Thermal memory
(1)
The minimum value of this trip is 1s regardless of the type of curve set (self-
protection).
(2)
These tolerances are based on the following assumptions:
- relay at full power (without start-up)
- preset trip time
≥
100 ms
(3)
no-trip time
(4)
the protection G is disabled for current values greater than 4In, where I4 < 0.5 In,
greater than 6 In, where 0.5 In
≤
I4 < 0.8 In and greater than 8 In where I4
≥
0.8 In.
For all cases not covered by the above hypotheses, the following tolerance values
apply:
Protections
Trip threshold
Trip time
L
Release between 1.05 and 1.25 x I1
± 20%
S
± 10%
± 20%
I
± 15%
≤
60ms
G
± 10%
± 20%
Others
± 20%