4.3 Installation of the fixed part of the withdrawable circuit-breaker
4.3.1
Preparation of the fixed part
Assembly of the anti-racking-in lock
Before installing the fixed part, it is necessary to check the presence of the anti-racking-in lock for circuit-breakers with different electrical
characteristics from those of the fixed part. If the anti-racking-in lock has been supplied separately, proceed to assemble it as follows:
– On the self-adhesive plate (4), find the assembly position of the stop bolts in relation to the circuit-breaker which has to be housed in the fixed
part.
– Insert the hexagonal-head screws (1) in the holes found in the previous item as shown in the figure.
– Fix the screws with the washers (2) and the hexagonal stops (3).
Make sure that the anti-racking-in lock corresponding to the one installed on the fixed part is present on the circuit-breaker (moving part).
– Anti-racking-in plate on the moving part (5).
Fig. 8
Table of the circuit-breaker weights (Kg.)
4.
Installation
4.1 Installation room
Install the circuit-breaker in a dry, dust-free, non-corrosive room, and
in such a way that it is not subject to shocks or vibrations. Where this
is not possible, install it inside a switchboard with a suitable degree of
protection.
For the preparation of the installation room, please refer to the "Overall
dimensions" paragraph, which gives information on the following points:
– minimum installation volumes of the circuit-breakers and derived
versions
– distances to be respected for circuit-breakers in compartments
– overall dimensions of the circuit-breakers
– fixing drillings
– compartment door drillings.
The installation, commissioning and any ordinary and extraordinary
maintenance have to be done by skilled personnel, with a detailed
knowledge of the apparatus.
4.2 Installation of the fixed circuit-breaker
Fix the circuit-breaker to a horizontal surface using the screws (M10 x
12 min.).
Fig. 7
With regard to lifting, follow the instructions: the circuit-breakers must be placed on a sturdy supporting surface and lifted, preferably, by means
of a special fork-lift truck. However, the use of ropes is allowed. In this case, the lifting ropes must be hooked up as shown in the figures (the lifting
plates are always supplied with the circuit-breaker).
Selective
Fixed version Withdrawable version
circuit-breaker
3 poles
4 poles
3 poles
4 poles
E2
50
61
78
93
E3
66
80
104
125
E4
97
120
147
170
E6
140
165
210
250