L3447
Emax DC
80/108
L3728
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000635R0002
14.2 PR120/D-M - COM communication module
14.2.1
General characteristics
Dedicated communication module for connecting the relay to a Modbus net, and for remote supervisory and control activities on the circuit-breakers.
14.2.2
Front view
- "Power" LED (lit when Vaux is installed)
- LED RX/TX (data send/receive signal).
14.2.3
Releases complete with the module
- optional for PR122/DC
- optional for PR123/DC
14.2.4
Power supply
The PR120/D-M - COM communication module is only powered by the relay if there is a 24V auxiliary voltage available.
14.2.5
Connection
Refer to fig. 45 in the wiring diagram provided in this manual.
14.2.6
Communication functions available
The communication function on the PR122/DC, PR123/DC releases with PR120/D-M - COM is listed in the table:
PR122/DC or PR123/DC + PR120/D-M - COM
Protocol
Modbus RTU
Physical interface
RS-485
Baud rate
9600 - 19200 bit/s
14.2.7
PR120/D-M - COM module menu
Parameter / Function
Values
Notes
Local/remote
Local/remote
Serial address
1 ... 247
247 default address
Baudrate
9600 bit/s
19200 bit/s
Physical protocol
8,E,1 - 8,0,1 - 8,N,2 - 8,N,1
Addressing
Modbus standard
ABB