If the PR122/DC was installed by the user, it is important, before closing the CB, to check the last line on the display when
the relay is turned on for the first time via a PR030/B battery unit. No TC disconnected messages must appear; if they do,
do not close the circuit-breaker and make the correct connections.
12.3.2 Test
Before putting into service, a test can be conducted by means of the specific "Auto test" function which
can be activated on the PR122/DC. A positive result is shown on the display.
Then a test can be conducted on the whole TC chain, again using the specific function (Trip test). A positive
result is shown by the circuit-breaker opening.To run a Trip Test, press the “i Test” button and the “Enter”
button simultaneously.
Check the open or closed state of the circuit-breaker on the same "PR122/DC Test" screen, by checking
that is closed and de-energized.
12.3.3 Checking connections
After making the initial settings, to ensure that the voltage sockets are properly connected on the power busbars, check
whether the release comes on when there is a voltage on the power input terminals and the CB is open and without any Vaux.
If this is not the case, there is no guarantee that the unit will function when powered from the busbar voltage without any
Vaux. Contact ABB SACE.
1/6
CB open
Auto Test
Trip Test (disabled)
CB status
Test
12.3 Putting into service
12.3.4 Initial settings
If the PR122/DC is supplied ready installed in the circuit-breaker, it is up to ABB SACE to set all the variables referring to the circuit-breaker or
the specific application correctly (e.g. type of circuit-breaker, Rating Plug size ...). For the PR120/V-PR120/LV module, set the Rated Voltage
suitably.
Note that ABB SACE defines each possible setting according the content of the paragraph on the default parameters (see par. 12.4.4).
Apart from this, it is absolutely indispensable for the user to modify the password and carefully define each modifiable
parameter, before putting the PR122/DC into service.
12.3.5 Password management
Specify a password? [0***]
To enter "EDIT" mode it is necessary to enter a four-figure numerical password. The values attributable to the password go from 0000 to 9999.
For the default password see par.12.4.4.
Select the value of the first figure ( between '0' and '9' ) by means of the
↑
and
↓
keys and press
↵
to confirm the figure and then move on to enter
the next one. After entering the fourth figure, check the password you have entered. If the password is correct, you go from the "READ" state to
the "EDIT" state. If the password is wrong, the message
Wrong password
appears and remains until the
ESC
key is pressed (or until an interval of 5 seconds has elapsed).
It is also possible to interrupt the password entry procedure by pressing the
ESC
key.
The password is valid for a maximum of two minutes from the last time a key was pressed.
Disabling the Password.
By setting the value of the password to [0000] (on the "Unit configuration" menu) the password prompt is disabled. It is therefore always possible
to switch from "READ" to "EDIT".
To enter a new password, select the "New Password" item on the "Settings/System" menu.
12.3.6 Replacing an electronic release
12.3.6.1
Installation
To complete the procedure for installing a PR122/DC unit, follow the steps below:
1.
With the circuit-breaker open and preferably isolated, install the protection unit on the circuit-breaker
2.
Power the unit ONLY from the PR030/B
3.
If there are no other errors, the display will show the message Configuration (configuration error) accompanied by the
yellow LED coming on permanently (warning)
4.
Enter the unit's "
Settings
" menu
5.
Select "
Circuit-breaker
"
6.
Select "
Unit installation
"
7.
Input the password
8.
Select "
Install
" and press "
ENTER
"
9.
When the red led flashes on and off and the message Installation (installation error) is displayed, remove the
PR030/B
10. Power the relay from any other source
11. Check for the absence of configuration errors.
12.3.6.2
Uninstalling
To complete the procedure for uninstalling a PR122/DC unit, follow the steps below:
1.
With the circuit-breaker open and/or isolated power the unit from the PR030/B
2.
Enter the unit's "
Settings
" menu
3.
Select "
Circuit-breaker
"
4.
Select "
Unit installation
"
5.
Input the password
6.
Select "
Uninstall
" and press "
ENTER
"
7.
Remove the PR030/B module
8.
Remove the PR122/DC unit from the circuit-breaker
9.
The remove the TC connector, proceed as indicated in the figure alongside.
It is not strictly necessary to complete the uninstalling procedure, but this enables the parameters relating to the circuit-breaker, such as contact
wear and others, otherwise these data would be lost. The data in question are then transmitted to the new PR122/DC unit installed on the same
circuit-breaker.