L3447
Emax DC
39/108
Model
Scale
Page No.
Doc. No.
Apparatus
1SDH000635R0002
L3728
You will be prompted to input a Password
complete the password entry procedure (par.12.3.5)
press the
↵
key (enter)
Change the date using the keys
↓
(arrow down)
↑
(arrow up) and confirm by pressing the
↵
key (enter).
Press ESC twice to return to the Main Menu.
Procedure requiring the confirmation of any programming
For instance, to change the Threshold of the Protection L, the correct sequence is as follows:
From the default page press ESC
to access the Main Menu
10:22:53
400A
I
Password
Enter password
0***
Date
Enter password
June 12, 2007
1/5
Protections settings
Measures
Settings
Protections
Menu
1/5
Protections settings
Measurements
Settings
Protections
Menu
1/6
Overload
S Protection
I Protection
L Protection
Protections
1/3
Time t1
Thermal memory
L Protection
Threshold I1
Password
Enter password
0***
From the Main Menu select the item PROTECTIONS
press the
↵
key (enter)
From the Protections Menu select the item PROTECTION L
press the
↵
key (enter)
From the Protection L Menu select the item THRESHOLD
press the
↵
key (enter)
You will be prompted to input a Password (par. 12.3.5)
complete the password entry procedure
press the
↵
key (enter)
Select the value you want from the list
and confirm pressing the
↵
key (enter).
Press ESC twice
Before accessing the Main Menu, the following box will appear:
Accept the new configuration
Reject the new configuration (the previous configuration is retained)
Change the previously input values.
To select the required option use the
↓
(arrow down),
↑
(arrow up) keys, and press
↵
(enter) to confirm.
O,4 In (320A)
Threshold I1
1/3
Confirm
Abort
Modify
Confirm
Programming